Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Valve size detection for
ICAD Only active if ID253
ICAD model is set to 1 (ICAD
600B) or 2 (ICAD 1200B) or 3
(ICAD TS).
0: No: Not active
1: Yes: Valve detection will
be started. The parameter
will automatically be set
back to ‘no’ and ID8 valve
conguration parameter will
be set to the detected valve
when detection has nished.
Valve size detection action
for ICAD Note: The allowed
value of the parameter var-
ies depends on the ICAD
model parameter (ID73)
12: ICADTS ICMTS 50/80;
11: ICADTS ICMTS20;
10: Pilot Valve CVE;
9: ICAD1200B ICM150;
8: ICAD1200B ICM125;
7: ICAD1200B ICM100;
6: ICAD1200B ICM65;
5: ICAD1200B ICM50;
4: ICAD1200B ICM40;
3: ICAD600B ICM32;
2: ICAD600B ICM25;
1: ICAD600B ICM20;
0: not congured No valve
selected. Alarm A1 will be-
come active
Denes what happens when
DI is ON (DI terminals are
shorted) Only active when
operation mode (ID2) is set
to ON/OFF.
1: Open valve: DI = OFF = >
Close ICM valve
0: Close valve: DI = OFF = >
Open ICM valve
When Operation mode (ID2)
is set to modulating.
1: On: Increasing Analog In-
put signal => Decreasing
opening degree
0: O: Increasing Analog In-
put signal => Increasing
opening degree
DI1 = ON, DI2= OFF => In-
creasing opening degree
DI1 = OFF, DI2 = ON => De-
creasing opening degree
DI1 = DI2 = OFF => Maintain
current position
DI1 = DI2 = ON => Maintain
current position
Note: Not active when Oper-
ation mode is set to ON/OFF.
For ON/OFF control refer to
DI funtion (ID23)
Active if operation mode
(ID2) is set to on/o
1: Yes: On/o mode with 2
step opening and/or 2 step
closing. Activates parame-
ters ID158...ID162
0: No: On/o mode with 1
step opening or closing,
without additional steps
while driving
ICM and ICMTS Motorized Valves with ICAD Actuators