Operatingguide
TermixATBTD
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................5
5.0MountinginstructionsTermixATBTDwall
cabinet............................................................6
5.1Mounting...........................................................6
6.0Design.............................................................8
6.1DesignTermixATBTD5pipes...................................8
6.2SchematicdiagramTermixATBTD5Pipes....................9
6.3DesignTermixATBTD4pipes...................................10
6.4SchematicdiagramTermixATBTD4Pipes....................11
7.0Controls..........................................................12
7.1DHWtemperaturecontrol........................................12
7.2Other.................................................................13
7.3Maintenance........................................................14
8.0Troubleshooting..............................................15
8.1Troubleshootingingeneral......................................15
8.2TroubleshootingDHW............................................15
8.3Disposal.............................................................16
9.0Declaration......................................................19
9.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
1

Questions and Answers

  • A
    Angel MurrayAug 3, 2025
    What to do if the thermostatic control valve does not close on Danfoss Termix AT BTD?
    • N
      Nicole HillAug 3, 2025
      If the thermostatic control valve on your Danfoss Boiler does not close, the temperature difference between the DH supply and the DHW set point might be too low. Try lowering the set point temperature or increasing the DH supply temperature.
  • J
    Joshua AndersonAug 8, 2025
    How to troubleshoot too little or no DHW in Danfoss Termix AT BTD Boiler?
    • C
      Crystal PearsonAug 8, 2025
      If you're experiencing too little or no domestic hot water (DHW) with your Danfoss Boiler, several factors could be responsible. Start by checking for a clogged strainer in the supply or return line and clean it. Ensure the DHW circulation pump is working correctly and set appropriately. A defective or clogged non-return valve can also cause issues, so replace or clean it. Confirm that there is electricity supplied to the boiler. If automatic controls are in place, verify their settings. Scaling of the plate heat exchanger may be the cause, requiring replacement or rinsing. Check the motorized valve, temperature sensors, and controller for defects, replacing as needed.
  • R
    Ronald WestAug 15, 2025
    Why is there a temperature drop during tapping in my Danfoss Boiler?
    • S
      Stacy WilliamsAug 15, 2025
      A temperature drop during tapping with your Danfoss Boiler may be due to scaling of the plate heat exchanger, in which case you should replace or rinse it out. Alternatively, the DHW flow might be larger than the substation was designed for, so try reducing the DHW flow.
  • A
    Aaron LewisAug 21, 2025
    What to do if some taps have hot water but not all in Danfoss Termix AT BTD Boiler?
    • E
      enguyenAug 21, 2025
      If you have hot water in some taps but not all with your Danfoss Boiler, it could be that DCW is being mixed with the DHW, possibly due to a defective thermostatic mixing valve; check and replace if necessary. Another cause might be a defective or clogged non-return valve on the circulation valve, which should be replaced or cleaned.
  • M
    Michelle ScottAug 27, 2025
    Why is the tap temperature too high in my Danfoss Termix AT BTD Boiler?
    • M
      Madeline MitchellAug 27, 2025
      If the tap temperature is too high and the DHW tap load is also too high on your Danfoss Boiler, the thermostatic valve may be adjusted to a level that is too high. Check and adjust the setting accordingly.

Summary

Safety Notes

Safety Notes - general

General safety instructions and warnings for installation and operation of the substation.

Mounting

Mounting

Instructions and specifications for mounting the substation, including connection sizes and dimensions.

Mounting instructions Termix AT BTD wall cabinet

Mounting

Detailed steps and diagrams for mounting the substation unit into its wall cabinet.

Design

Design Termix AT BTD 5 pipes

Overview and diagram of the Termix AT BTD 5-pipe system design.

Schematic diagram Termix AT BTD 5 Pipes

Schematic representation of the Termix AT BTD 5-pipe system components and connections.

Design Termix AT BTD 4 pipes

Overview and diagram of the Termix AT BTD 4-pipe system design.

Schematic diagram Termix AT BTD 4 Pipes

Schematic representation of the Termix AT BTD 4-pipe system components and connections, including technical parameters.

Controls

DHW temperature control

Details on domestic hot water temperature control, including the AB-QM controller settings.

Other

Information on other components like cold water meter fitting piece and siphon.

Maintenance

Recommended maintenance tasks and schedule for the substation, including strainers and safety valves.

Troubleshooting

Troubleshooting in general

General checks and basic troubleshooting steps for operating disturbances.

Troubleshooting DHW

Specific problems and solutions related to Domestic Hot Water (DHW) supply and temperature.

Disposal

Guidelines for proper dismantling and disposal of the substation components.

Declaration

Declaration of conformity

Official EU Declaration of Conformity for the Termix substations.

Danfoss Termix AT BTD Specifications

General IconGeneral
BrandDanfoss
ModelTermix AT BTD
CategoryBoiler
LanguageEnglish