Instructions
Termix VMTD-F-B
District heating substation for
direct heating and
instantaneous domestic hot water
Table of Contents
Declaration of conformity ............................... 2
Safety notes ...................................................... 3
Storage .............................................................. 3
Disposal ............................................................. 3
Mounting .......................................................... 4
Pipe connections ................................................ 4
Electrical connection .......................................... 5
Filling, start-up ................................................... 5
Design ............................................................... 6
Schematic diagram (example) ........................ 6
Control .............................................................. 7
Maintenance ..................................................... 8
Troubleshooting DHW ..................................... 9
Troubleshooting HE ...................................... 10

Other manuals for Danfoss Termix VMTD-F-B

Questions and Answers

  • W
    whitedavidAug 15, 2025
    How to troubleshoot too little or no DHW in Danfoss Termix VMTD-F-B Water Heater?
    • V
      vlarsonAug 15, 2025
      If your Danfoss Water Heater isn't producing enough or any domestic hot water (DHW), several factors could be the cause: * A clogged strainer in the supply or return line may be restricting flow. Cleaning the strainer(s) can resolve this. * The DHW circulation pump may be faulty or set too low. Inspect the circulation pump. * A defective or clogged non-return valve could be the issue. In this case, replace or clean the valve. * Check if there is electricity.
  • T
    Teresa WilcoxAug 18, 2025
    What to do if hot water in some taps but not in all in Danfoss Termix VMTD-F-B?
    • H
      hernandezsamuelAug 19, 2025
      If your Danfoss Water Heater is producing hot water in some taps but not others, it could be due to: * DCW mixing with DHW because of a defective thermostatic mixing valve or non-return valve. Check and replace if necessary. * A defective or clogged non-return valve on the circulation valve. Replace or clean it.
  • E
    Emily WilliamsAug 22, 2025
    Why is DH supply temperature too high in Danfoss Termix VMTD-F-B Water Heater?
    • M
      mooreanaAug 22, 2025
      If the DH supply temperature from your Danfoss Water Heater is too high, it might be due to: * Incorrect thermostat or automatic control settings. Adjust the automatic controls, referring to their specific instructions. * A defective controller. Contact the automatic controls manufacturer or replace the regulator. * A defective sensor on the self-acting thermostat. Replace the thermostat or just the sensor.
  • X
    xbarnettAug 26, 2025
    Why temperature drop during tapping in Danfoss Termix VMTD-F-B?
    • J
      John DeanAug 26, 2025
      If you're experiencing a temperature drop during tapping with your Danfoss Water Heater, consider these potential causes: * Scaling of the plate heat exchanger. You may need to replace or rinse it out. * The DHW flow is larger than the substation was designed for. Reduce the DHW flow.
  • S
    Stephanie VillegasAug 28, 2025
    Why is DH supply temperature too low in Danfoss Termix VMTD-F-B?
    • P
      Pamela MartinAug 29, 2025
      If the DH supply temperature from your Danfoss Water Heater is too low, it could be caused by: * Incorrect settings on the automatic controls. Adjust the automatic controls according to their instructions. * A defective controller. In this case, contact the automatic controls manufacturer or replace the controller. * A defective sensor on the self-acting thermostat. Replace the thermostat or just the sensor. * Incorrect placement or fitting of the outdoor temperature sensor. Adjust the location of the outdoor temperature sensor. * A clogged strainer. Clean the gate/strainer.
  • A
    Alyssa KimSep 1, 2025
    What to do if too little or no heat from Danfoss Termix VMTD-F-B?
    • K
      Krista HebertSep 1, 2025
      If your Danfoss Water Heater is providing too little or no heat, consider the following: * A clogged strainer in the DH or HE circuit (radiator circuit). Clean the gate/strainer. * A clogged filter in the heat meter on the DH circuit. Clean the filter (after consulting the DH plant operator). * A defective or wrongly adjusted differential pressure controller. Check the operation of the differential pressure controller and clean the valve seat if required.
  • D
    David SimpsonSep 7, 2025
    What to do if some taps have hot water but not all in my Danfoss Water Heater?
    • M
      Mrs. Amy Perkins DDSSep 7, 2025
      If you're experiencing hot water in some taps but not others with your Danfoss Water Heater, it could be due to a couple of reasons. Firstly, check for backflow of cold water mixing with the hot water, possibly caused by a defective thermostatic mixing valve; if so, replace it. Secondly, inspect the circulation valve for a defective or clogged non-return valve; replace or clean as necessary.
  • J
    john18Sep 12, 2025
    Why does the temperature drop when tapping water from my Danfoss Water Heater?
    • J
      Joseph RosarioSep 12, 2025
      A temperature drop during tapping with your Danfoss Water Heater may occur due to scaling of the plate heat exchanger, requiring replacement or rinsing. Alternatively, the DHW flow might be larger than the substation's design capacity, so reduce the DHW flow.

Summary

Safety Notes

Warning of Hot Surface

Caution regarding hot surfaces on the substation to prevent skin burns.

Warning of High Pressure and Temperature

Notes on maximum operating pressure and temperature limits for safety.

Mounting

Pipe Connections

Electrical Connection

Filling and Start-up

Schematic Diagram (Example)

Control

DHW Temperature Control

Guidance on setting domestic hot water temperature to optimize usage and prevent scale.

Maintenance

Safety Valve

Purpose and recommended checks for the safety valve to protect against overpressure.

Troubleshooting DHW

Troubleshooting HE

Danfoss Termix VMTD-F-B Specifications

General IconGeneral
BrandDanfoss
ModelTermix VMTD-F-B
CategoryWater Heater
LanguageEnglish