1.10 Specifications
1.10.1 Mains Suply 200 - 400 V
According to . international
standards
Type 2803 2805 2807 2811 2815 2822 2822
PD2
2840 2840
PD2
Output current I
INV.
[A] 2.2 3.2 4.2 6.0 6.8 9.6 9.6 16 16
(3 x 200-240V)
I
MAX
(60s) [A] 3.5 5.1 6.7 9.6 10.8 15.3 10.6 25.6 17.6
Output power
(230 V)
S
INV.
[KVA] 0.9 1.3 1.7 2.4 2.7 3.8 3.8 6.4 6.4
Typical shaft out-
put
P
M,N
[kW] 0.37 0.55 0.75 1.1 1.5 2.2 2.2 3.7 3.7
Typical shaft out-
put
P
M,N
[HP] 0.5 0.75 1.0 1.5 2.0 3.0 3.0 5.0 5.0
Max. cable cross
section, motor
[mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6
Input current I
L,N
[A] 5.9 8.3 10.6 14.5 15.2 - 22.0 - 31.0
(1 x 220-240 V)
I
L,MAX
(60s)
[A]
9.4 13.3 16.7 23.2 24.3 - 24.3 - 34.5
Input current I
L,N
[A] 2.9 4.0 5.1 7.0 7.6 8.8 8.8 14.7 14.7
(3 x 200-240 V)
I
L,MAX
(60s)
[A]
4.6 6.4 8.2 11.2 12.2 14.1 9.7 23.5 16.2
Max. cable cross
section, power
[mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6
Max. pre-fuses IEC/UL [A] 20/2
0
20/2
0
20/2
0
20/2
0
20/2
0
20/2
0
35/3
5
25/2
5
50/5
0
Efficiency [%] 95 95 95 95 95 95 95 95 95
Power loss at
100% load
[W] 24 35 48 69 94 125 125 231 231
Weight [kg] 2.0 2.0 2.0 2.0 2.0 3,7 6.0 6.0 18.5
0
Enclosure type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP
20/
NEM
A 1
1.10.2 Mains Supply 380 - 480 V
According to international
standards
Type 2805 2807 2811 2815 2822 2830
Output current I
INV.
[A] 1.7 2.1 3.0 3.7 5.2 7.0
(3 x 380-480V)
I
MAX
(60s) [A] 2.7 3.3 4.8 5.9 8.3 11.2
Output power (400
V)
S
INV.
[KVA] 1.1 1.7 2.0 2.6 3.6 4.8
Typical shaft out-
put
P
M,N
[kW] 0.55 0.75 1.1 1.5 2.2 3.0
Typical shaft out-
put
P
M,N
[HP] 0.75 1.0 1.5 2.0 3.0 4.0
Max. cable cross
section, motor
[mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10
Input current I
L,N
[A] 1.6 1.9 2.6 3.2 4.7 6.1
(3 x 380-480 V)
I
L,MAX
(60s)[A] 2.6 3.0 4.2 5.1 7.5 9.8
Max. cable cross
section, power
[mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10
Max. pre-fuses IEC/UL [A] 20/20 20/20 20/20 20/20 20/20 20/20
Efficiency [%] 96 96 96 96 96 96
Power loss at 100%
load
[W] 28 38 55 75 110 150
Weight [kg] 2.1 2.1 2.1 2.1 3.7 3.7
Enclosure type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
1 Quick Guide VLT 2800 Quick Guide
28
MG.28.M1.02 - VLT
®
is a registered Danfoss trademark
1

Other manuals for Danfoss VLT 2811

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2811 and is the answer not in the manual?

Danfoss VLT 2811 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2811
CategoryDC Drives
LanguageEnglish

Related product manuals