VL Serie 2800 and VL Serie 6000 Modbus RTU
method of checking for errors, parity checking is
seldom used in Modbus RTU networks.
571 Modbus communications timeout
(M.BUS COM.TIME.)
Value:
10 ms - 2000 ms
j 100 ms
Function:
This parameter determines the maximum amount
of time that the drives Modbus RTU will wait
between characters that are sent by the master
controller. When this amount of time expires, the
drives Modbus RTU interface will assume that it
has received the entire message.
Description of choice:
Generally, the value of 100 ms is sufficient for Modbus
RTU networks, although some Modbus RTU networks
may operate on a timeout value as short as 35 ms.
If this value is set too short, the drivesModbusRTU
interface may miss a part of the message. Since the
CRC check will not be valid, the drive will ignore the
message. The resulting retransmissions of messages
will slow communications on the network.
If this value is set too long, the drive will wait longer
than necessary to determine that the message is
completed. This will delay the drives response to the
message and possibly cause the master controller to
time out. The resulting retransmissions of messages
will slow communications on the network.
MG.10.S1.22 - VLT is a registered Danfoss trademark