Frame size D1 D2 D3 D4
90-110 kW
(380-500 V)
37-132 kW
(525-690 V)
132-200 kW
(380-500 V)
160-315 kW
(525-690 V)
90-110 kW
(380-500 V)
37-132 kW
(525-690 V)
132-200 kW
(380-500 V)
160-315 kW
(525-690 V)
IP
NEMA
21
Type 1
54
Type 12
21
Type 1
54
Type 12
00
Chassis
00
Chassis
Shipping dimensions
Height 650 650 650 650 650 650
Width 1730 1730 1730 1730 1220 1490
Depth 570 570 570 570 570 570
Frequency converter
dimensions
Height 1209 1209 1589 1589 1046 1327
Width 420 420 420 420 408 408
Depth 380 380 380 380 375 375
Max
weight
[kg]
104 104 151 151 91 138
Table 3.1 Mechanical dimensions [mm], frame size D
Frame size
E1 E2 F1 F2 F3 F4
250-400 kW
(380-500 V)
355-560 kW
(525-690 V)
250-400 kW
(380-500 V)
355-560 kW
(525-690 V)
450-630 kW
(380-500 V)
630-800 kW
(525-690 V)
710-800 kW
(380-500 V)
900-1200 kW
(525-690 V)
450-630 kW
(380-500 V)
630-800 kW
(525-690 V)
710-800 kW
(380-500 V)
900-1200 kW
(525-690 V)
IP
NEMA
21, 54
Type 12
00
Chassis
21, 54
Type 12
21, 54
Type 12
21, 54
Type 12
21, 54
Type 12
Shipping
dimensions
Height
840 831 2324 2324 2324 2324
Width 2197 1705 1569 1962 2159 2559
Depth 736 736 1130 1130 1130 1130
Frequency
converter
dimensions
Height 2000 1547 2204 2204 2204 2204
Width 600 585 1400 1800 2000 2400
Depth 494 498 606 606 606 606
Max
weight
313 277 1004 1246 1299 1541
Table 3.2 Mechanical dimensions [mm], frame sizes E and F
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16 17
3 3