Items Supplied
Male LCP 21-RJ45 converter plug (1).
Female LCP 21-RJ45 converter plug (1).
Thread cutting screws (4).
More Items Required
Local control panel (LCP 21), ordering number
132B0254.
Installation
1. Mount the male LCP 21-RJ45 converter plug on the
frequency converter and fasten with 2 thread cutting
screws, see Illustration 1.1.
2. Tighten the screws to 1.3 Nm (11.5 in-lb).
Illustration 1.1 Mounting the Male LCP 21-RJ45 Converter Plug
3. Mount the female LCP 21-RJ45 converter plug on the
LCP 21 (local control panel), and fasten with 2 thread
cutting screws, see Illustration 1.2.
4. Tighten the screws to 1.3 Nm (11.5 in-lb).
Illustration 1.2 Mounting the Female LCP 21-RJ45 Converter Plug
5. Connect the 2 LCP 21-RJ45 converter plugs with a
shielded Ethernet cable, maximum 15 m (49.2 ft)
long.
Installation Instructions
VLT
®
Control Panel LCP 21 - RJ45 Converter Kit
Danfoss A/S © 08/2017 All rights reserved. MI07M102