Items Supplied
LCP cables with 2 M12 connectors (90° male connector and straight female connector). Cable lengths: 3 m, 5 m, and 10 m
(10 ft, 16 ft, 33 ft). See also Table 1.1.
Blind cover with M12 female connector.
Base plate with D-sub connector and M12 male connector.
Two gaskets and 1 nut for the D-sub connector.
Intermediate cover with the front cover.
Disassembly tool.
Length [m (ft)] Ordering number
3 (10) 134B5223
5 (16) 134B5224
10 (33) 134B5225
Table 1.1 Cable Ordering Numbers
More Items Required
Local control panel (LCP).
Four M4 self-tapping screws for mounting.
NOTICE
This instruction is valid for frequency converters that were ordered with the LCP. Front covers of frequency converters that
were ordered without LCPs do not have holes for mounting the blind covers.
Safety Instructions
For important information about safety precautions for installation, refer to the product-specic operating guide.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not
powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time
after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to
other frequency converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The minimum duration of waiting time is specied in .
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the
capacitors are fully discharged.
Installation Instructions
Remote Mounting of LCP
VLT
®
HVAC Drive FC 102
Danfoss A/S © 11/2017 All rights reserved. MI05A202
Question and Answer IconNeed help?

Do you have a question about the Danfoss LCP and is the answer not in the manual?

Danfoss LCP Specifications

General IconGeneral
BrandDanfoss
ModelLCP
CategoryControl Panel
LanguageEnglish

Summary

Items Supplied

More Items Required

Safety Instructions

Discharge Time Warning

Warning about high voltage in DC-link capacitors and required waiting time before service.

Mechanical Installation

Installing the Blind Cover

Instructions for removing the front cover and installing the blind cover on the frequency converter.

Mounting the Remote LCP

Steps for drilling holes, installing the base plate, and securing the remote LCP to the wall.

Electrical Installation

Areas with Gaskets on the Remote Unit