Surroundings:
Enclosure IP 20
Enclosure kit available IP 21, TYPE 1
Vibration test 1.0 g
Max. relative humidity 5% - 95%(IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature Max. 40 °C
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation 0 °C
Minimum ambient temperature at reduced performance - 10 °C
Temperature during storage/transport -25 - +65/70 °C
Maximum altitude above sea level without derating 1000 m
Maximum altitude above sea level with derating 3000 m
Derating for high altitude, see section on special conditions
Safety standards EN/IEC 61800-5-1, UL 508C
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions
Quick Guide VLT Micro Drive Quick Guide
18 MG.02.B6.02 - VLT
®
is a registered Danfoss trademark
11

Other manuals for Danfoss VLT Micro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro and is the answer not in the manual?

Danfoss VLT Micro Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro
CategoryMedia Converter
LanguageEnglish

Related product manuals