EasyManuals Logo

Danfoss VLT Manual

Danfoss VLT
2 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
Danfoss Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80, www.danfoss.com/drives • E-mail: info@danfoss.com
MF004A02 VLT® is a trademark of Danfoss A/S Produced by KKM 2007.10
Programming for No-Flow detection
is simplified with a number of para-
meters that are pre-programmed into
the drive. Prior to programming this
feature, commission the drive by
using the parameters in the Quick
Menu Q2 Quick Set-Up. Then perform
the following steps for programming
No-Flow detection:
Par.# Description
Settings
Comments
Factory
setting
Recommended
setting
22-20 Low Power Auto Set-up Disable Enable Close the outlet valve for the pump before starting Auto Set-up. Select Enable
and follow the instruction on the LCP. After Auto Set-up is complete, open the
pump outlet valve.
The following parameters are accessed through the Main Menu and will be stored after pressing the [OK] key to save the results after the auto-tuning
22-33 Low Speed
[Hz]
When Low Power Auto Set-up is used, 50% of the drives maximum frequency
will be stored here. This can be manually edited, if desired.
22-34 Low Speed Power [kW] When Low Power Auto Set-up is used, the output power measured under
no-flow conditions at 50% speed will be stored here. This can be manually
edited, if desired.
22-37 High Speed
[Hz]
When Low Power Auto Set-up is used, 85% of the drives maximum frequency
will be stored here. This can be manually edited, if desired.
22-3 High Speed Power [kW] When Low Power Auto Set-up is used, the output power measured under
no-flow conditions at 85% speed will be stored here. This can be manually
edited, if desired.
These parameters are used after Auto Set-up and the No-Flow feature is operating
22 - 30 No-Flow Power When the drive is running, this parameter will show the power level that will
be interpreted as producing no flow at the current motor speed.
22 - 31 Power Correction
Factor
100% 110% This parameter is used to raise or lower the no-flow power curve to the
percentage entered here. Values above 100% help ensure the drive reliably
detects no-flow.
The following parameters determine the action that the drive will take if a no flow condition is detected
22-21 Low Power
Detection
Disable Enable To activate no-flow based on power
22-23 No-Flow Function Off Sleep Mode/
Warning/Alarm
Select action
22-24 No-Flow Delay 10 sec. Set the time delay before the drive will perform the No-Flow Function.
Generally set longer than the decel ramp time.
The following parameters give and indication to a BMS if a no flow condition is detected
5-40 Function Relay [190] No-Flow
Program one of the relays to selection [190], No-Flow. The selected relay will
be activated when No-Flow occurs.
Digital Output [190] No-Flow
A digital output can be used to indicate a no flow condition. Use the
parameter that sets the function of the desired digital output.
The following are used if No-Flow is reported via serial communications
Protocol Warning Word
BACnet BV:77 No Flow
LonWorks nvoWarningword Bit 37
Modbus RTU TU Register 16930 Bit 6 = 1
Programming No-Flow detection

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals