46210/46220-0998 <90-00036> PAGE 63
The display for control subgroup 1 (CPM 1) shows whether the
control points are closed (C) or open (O). The letter D indicates a
control point operation that has not been acknowledged.
See the command ACKNOWLEDGE for information on acknowl-
edging alarms and control points.
TERMINOLOGY
Purpose:
Shows or changes the terminology being used to display alarms,
either SG (instead of MAT) or MAT (instead of SG). Refer to the
beginning of the Input Commands for more information.
Format:
TERMINOLOGY
TERMINOLOGY SG
Output Response:
Only the command TERMINOLOGY gives a response and that
is to show if the terminology is to be displayed as SG or MAT.
TIME OUT
Purpose:
Sets the time-out after which the 46210/46220 will return to the
default protocol (DCPF).
The default time is 10 minutes.
Format:
TIME OUT
TIME OUT #
Remarks:
The command TIME OUT will display the number of minutes
for which the time-out is set.
The command TIME OUT followed by a number will set the
time-out period. the # can be a number from 1-30; the number
represents minutes.
Output Response:
Both commands show the number of minutes for which the time-
out is set.
PRINTER SYNTAX