10-2014 gForce User Manual ● 59
NOTE:
The Temp Setpoint range is from 45.0°F to 105.0°F (factory setting
is 72.0°F).
The Temp Deadband range is from 2.0°F to 5.0°F (factory setting is 2.0°F).
Superheat setpoint range is from 5.0°F to 15.0°F (factory setting is 6.0°F).
To change the values press the ENTER key to move the cursor to the desired input
(Temp Setpoint). The cursor will flash next to the current entered value.
Press the UP or DOWN key to change the value. Once the value has been changed to
the desired value, press the ENTER key. The cursor will move to the next input (Temp
Deadband).
Change the value (if required) using the same procedure or press the ENTER key to
return the cursor to the top of the screen (it will flash next to the title – Rack Temp
Setpoints).
To see the next screen, press the DOWN key.
The following will appear if the fans are controlled based on Rack Temperature (values
are for reference only):
This setpoint will control the fan motor modulation.