10-2014 gForce User Manual ● 91
Once the selections have been made, with the cursor on the title line, Press the DOWN
key to advance to the next screen.
The following screen will be displayed (values are for reference only):
Press the ENTER key to move through the alarm/message inputs.
Press the UP or DOWN keys to change the alarm/message.
The following selections are available:
Firestat:
100 150°F (factory setting is 100°F)
Hi Temp Alarm:
Yes or No (factory setting is Yes)
Set Point:
70 - 120°F (factory setting is 80°F)
Lo Temp Alarm:
Yes or No (factory setting is Yes)
Set Point:
55 - 75°F (factory setting is 60°F)
NOTE:
If No is selected for the Hi or Low Temp, the setpoint will not be
displayed.
Once the selections have been made, with the cursor on the title line, Press the DOWN
key to advance to the next screen.