DKG-175 User Manual V-1 (24.07.2017)
- 6 -
Although the unit is protected against electromagnetic disturbance, excessive disturbance can affect the
operation, measurement precision and data communication quality.
ALWAYS remove plug connectors when inserting wires with a screwdriver.
Fuses must be connected to the power supply and phase voltage inputs, in close
proximity of the unit.
Fuses must be of fast type with a maximum rating of 6A.
Use cables of appropriate temperature range.
Use adequate cable section, at least 0.75mm
2
(AWG18).
Follow national rules for electrical installation.
Do not install the unit close to high electromagnetic
noise emitting devices like contactors, high current
busbars, switch mode power supplies and the like.