PGM
Parameter Definition
Unit
Fact.Set
Description
P_018
Low Oil Pressure
Warning
bar
1.4
If the oil pressure measured from the analog input
falls below this limit, this will generate a LOW OIL
PRESSURE SENDER warning.
P_019
Low Oil Pressure
Shutdown
bar
1.0
If the oil pressure measured from the analog input
falls below this limit, this will generate a LOW OIL
PRESSURE SENDER alarm is generated and the
engine stops.
P_020
High Temperature
Warning
°C
95
If the coolant temperature measured from the
analog input goes over this limit, this will generate
a HIGH TEMPERATURE SENDER warning.
P_021
High Temperature
Shutdown
°C
98
f the coolant temperature measured from the
analog input goes over this limit, this will generate
a HIGH TEMPERATURE SENDER alarm and the
engine will stop.
P_022
Low Fuel Warning
%
20
If the fuel level measured from the analog input
falls below this limit, a LOW FUEL LEVEL
SENDER warning is generated.
P_023
Low Fuel Shutdown
%
10
the fuel level measured from the analog input falls
below this limit, a LOW FUEL LEVEL SENDER
shutdown alarm is generated and the engine stops.
P_024
High Oil Temperature
Warning
°C
100
If the oil temperature measured from the analog
input goes over this limit, this will generate a HIGH
OILTEMPERATURE SENDER warning.
P_025
High Oil Temperature
Shutdown
°C
120
f the oil temperature measured from the analog
input goes over this limit, this will generate a HIGH
OIL TEMPERATURE SENDER alarm and the
engine will stop.
P_026
Oil Pressure Sender
type
-
1
This parameter selects the oil pressure sender
type.
0: Non standard sender. The sender
characteristics are defined in Sender
Characteristics table.
1: VDO 0-7 bars (10-180 ohms)
2: VDO 0-10 bars (10-180 ohms)
3: DATCON 0-7 bars (240-33 ohms)
4: DATCON 0-10 bars (240-33 ohms)
5: DATCON 0-7 bars (0-90 ohms)
6: DATCON 0-10 bars (0-90 ohms)
7: DATCON 0-7 bars (75-10 ohms)
P_027
Coolant Temp.
Sender Type
-
1
This parameter selects the temperature sender
type:
0: The sender characteristics are defined in
Sender Characteristics table.
1: VDO
2: DATCON DAH type
3: DATCON DAL type
P_028
Oil Temp. Sender
Type
-
1
This parameter selects the temperature sender
type:
0: The sender characteristics are defined in
Sender Characteristics table.
1: VDO
2: DATCON DAH type
3: DATCON DAL type