WARNING: ELECTRICITY CAN KILL
ALWAYS disconnect the power BEFORE connecting
the unit.The fuse rating should be 6 Amps.
1) ALWAYS remove the plug connectors when inserting wires with a
screwdriver.
2) An appropriate and readily accessible set of disconnection devices
(e.g. automatic fuses) MUST be provided as part of the installation.
3) The building mains supply MUST incorporate appropriate short-circuit
backup protection (e.g. a fuse or circuit breaker) of High Breaking
Capacity (HBC, at least 1500A).
Use cables of adequate current carrying capacity (at least 0.75mm
2
)
and temperature range.
WARNING: THE UNIT IS NOT FUSED.
Use external fuses for Mains phases: L1,L2,L3,
Generator phase: L1,L2,L3, Battery positive: BAT(+).
Install the fuses as nearly as possible to the unit in a
place easily accessible for the user.
The fuse rating should be 6 Amps.
Engine body must be grounded for correct operation of
the unit, otherwise incorrect voltage and frequency
measurements may occur.