PGM
Parameter Definition
Unit
Fact.Set
Description
P_094
J1939 Enable
-
0
0: The J1939 port is inoperative.
1: The analog measurements (oil, temp, rpm) are
picked_up from the ECU. If the ECU communication
is lost, then the engine will be stopped.
P_095
J1939 Engine Type
-
0
00: GENERIC ENGINE TYPE
16: CUMMINS CM850
32: DETROIT DIESEL
48: DEUTZ Generic
49: DEUTZ EMR2
50: DEUTZ EMR3
64: JOHN DEERE
80: PERKINS
81: PERKINS ADEM 3
82: PERKINS ADEM 1.3
96: VOLVO (with CIU unit)
97: VOLVO EMS2
98: VOLVO EDC4
112: CATERPILLAR ADEM II/III
128: SCANIA S6
129: SCANIA Single Speed
130: SCANIA All Speed
144: IVECO
160: MTU MDEC 302
161: MTU MDEC 201
162: MTU MDEC 303
163: MTU MDEC 304
164: MTU MDEC 505
176: BOSCH Generic
177: BOSCH EDC 731
178: BOSCH EDC 9.3
Other values: Reserved. Do not use.
P_096
J1939 Speed Adjust
%
50
This parameter adjusts the speed of an ECU
controlled engine by +/- 8%.
P_097
VOLVO Speed
Toggle
-
-
This program parameter is not stored, but only used
in order to activate the primary or secondary speed
selection operation of a Volvo EMS-II engine control
unit.
0: Initiate the primary speed select operation
1: Initiate the secondary speed select operation
Below parameters are applicable to J1939 enabled
versions only.