Tab.66
On > > Installation Setup > CU-GH08 > Gas fired appliance > Parameters, counters, signals > Parameters
Code Text display Description Adjustment range 10 15 25 25/28
MI
35
AP001 BL input setting Blocking input setting (1:
Full blocking, 2: Partial
blocking, 3: User reset
locking)
1 = Full blocking
2 = Partial blocking
3 = User reset locking
1 1 1 1 1
AP002 Manual Heat
Demand
Enable manual heat
demand function
0 = Off
1 = With setpoint
2 = TOutdoor Control
0 0 0 0 0
AP003 Flue Valve Wait
Time
Wait time after burner
command to open flue gas
valve
0 Sec – 255 Sec 0 0 0 0 0
AP006 Min. water
pressure
Appliance will report low
water pressure below this
value
0 bar – 6 bar 0.8 0.8 0.8 0.8 0.8
AP008 Time release
signal
The appliance will wait x sec
(0=off) for the release
contact to close in order to
start the burner
0 Sec – 255 Sec 0 0 0 0 0
AP009 Service hours
burner
Burning hours before raising
a service notification
0 Hours – 51000 Hours 6000 6000 6000 6000 6000
AP010 Service
notification
The type of service needed
based on burn and powered
hours
0 = None
1 = Custom notification
2 = ABC notification
0 0 0 0 0
AP011 Service hours
mains
Hours powered to raise a
service notification
0 Hours – 51000 Hours 35000 35000 3500
0
35000 35000
AP016 CH function on Enable central heating heat
demand processing
0 = Off
1 = On
1 1 1 1 1
AP017 DHW function on Enable domestic hot water
heat demand processing
0 = Off
1 = On
1 1 1 1 1
AP026 Setpoint manual
HD
Flow temperature setpoint
for manual heat demand
10 °C – 90 °C 40 40 40 40 40
AP063 CH Set Max
System
Maximum flow temperature
setpoint for burning at
central heating
20 °C - 90 °C 90 90 90 90 90
AP102 Boiler Pump
function
Configuration of the boiler
pump as zone pump or
system pump (feed lowloss
header)
0 = No
1 = Yes
0 0 0 0 0
DP003 Abs. max fan
DHW
Maximum fan speed on
Domestic Hot Water
1000 Rpm – 7000 Rpm 3300 4500 5600 6200 6200
DP020 Postrun DHW
pump/3wv
Post run time of the DHW
pump/3 way valve after
DHW production
0 Sec – 99 Sec 10 10 10 10 10
GP007 Fan RPM Max CH Maximum fan speed during
Central Heating mode
1400 Rpm – 7000 Rpm 3300 4500 5600 4600 6200
GP008 Fan RPM Min Minimum fan speed during
Central Heating + Domestic
Hot Water mode
1400 Rpm – 4000 Rpm 1800 1800 1850 1850 1850
GP009 Fan RPM Start Fan speed at appliance start 1000 Rpm – 4000 Rpm 3300 3700 3000 3000 4000
GP010 GPS Check Gas Pressure Switch check
on/off
0 = No
1 = Yes
0 0 0 0 0
GP017 Max power Maximum power percentage
in kilo Watt
0 kW – 80 kW 24 24 32.3 32.3 40.3
GP021 Temp diff
Modulating
Modulate back when delta
temperature is large then
this treshold
10 °C – 40 °C 25 25 25 25 25
9 Settings
7686707 - v.01 - 06092018 AMC 89

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DeDietrich AMC 15 and is the answer not in the manual?

DeDietrich AMC 15 Specifications

General IconGeneral
BrandDeDietrich
ModelAMC 15
CategoryBoiler
LanguageEnglish

Related product manuals