Alternative Configuration 2
Alternative Configuration 3
Coolant Temperature Switch
DPF Regeneration
Interlock
Alternative Configuration 1
Oil Pressure Sensor Open Circuit
Battery High Volts Warning
Over Speed Overshoot Alarm
Battery Low Volts Warning
Open Generator Output Pulse
Over Frequency Overshoot Alarm
Display Heater Fitted and Active
Preheat During Preheat Timer
DPF Auto Regeneration Inhibit
Charge Alternator Shutdown
Preheat Until End of Crank
Charge Alternator Warning
Preheat Until End of Safety Timer
Preheat Until End of Warming
DPF Regeneration in Progress
Close Generator Output
Pulse
DPF Regen Interlock Active
Temperature Sensor Open Circuit
Waiting for Manual Restore
Flexible Sensor C High Alarm
Fuel Tank Bund Level High
Flexible Sensor C High Pre-Alarm
Flexible Sensor C Low Pre-Alarm
Flexible Sensor C Low Alarm
Generator Under Frequency
Warning
Generator Over Frequency
Warning
Generator Low Voltage Warning
Fuel Sensor High Pre-Alarm
Generator High Voltage Warning
Fuel Sensor Low Pre-Alarm
Flexible Sensor A High Alarm
Flexible Sensor A High Pre-Alarm
Flexible Sensor A Low Alarm
Flexible Sensor A Low Pre-Alarm
Generator High Voltage
Alarm
Flexible Sensor A Open Circuit
Generator Low Voltage
Alarm
Over Current Immediate
Warning
Delayed Over Current Alarm
Low Coolant Level Open Circuit
High Coolant Temp
Shutdown
Analogue Input A (Digital)
Low Oil Pressure Shutdown
Analogue Input B (Digital)
High Coolant Temp Pre-Alarm
Analogue Input C (Digital)
Functionality in DSE4510 MKII & DSE4520 MKII
Functionality in DSE4520 MKII only
140 mm x 113 mm x 43 mm
(5.5” x 4.4” x 1.7”)
118 mm x 92 mm
(4.6” x 3.6”)
Tightening Torque: 0.5 Nm (4.5 lb-in)
Conductor Size: 0.5 mm² to 2.5 mm²
(AWG 20 to AWG 13)
NOTE: A larger version of the typical wiring diagram is included in
the product’s operator manual. Refer to DSE Publication:
057-260 DSE4510 MKII & DSE4520 MKII Operator Manual
NOTE: Terminals 25, 26, 27 & 28 are not fitted to the DSE4510 MKII
DEEP SEA ELECTRONICS
DSE4510 MKII & DSE4520 MKII Installation Instructions
Applicable to module version 3.0.0 and upwards.
EDITING A PARAMETER
• Press the Stop/Reset Mode ( - ) and Auto Mode () buttons together
to enter the editor mode.
• Press the Up or Down navigation buttons to cycle through the front
panel editor in increments of 100.
• Press the Manual/Start Mode ( + ) or Stop/Reset Mode ( - ) buttons to
cycle through the front panel editor in increments of 1.
• When viewing the parameter to be edited, press the Auto Mode () button
and the value begins to flash.
• Press the Manual/Start Mode ( + ) or Stop/Reset Mode ( - ) navigation
buttons to adjust the value to the required setting.
• Press the Auto Mode () button to save the current value, the value
ceases flashing.
• Press and hold the Auto Mode () button to save and exit the editor, the
configuration icon is removed from the display.
NOTE: Pressing and holding the Manual/Start Mode ( + ) or
Stop/Reset Mode ( - ) buttons will give auto-repeat functionality.
NOTE: More comprehensive module configuration is possible via PC
configuration software. For further details of module configuration, refer
to DSE Publication: 057-258 DSE4510 MKII & DSE4520 MKII
Configuration Suite PC Software Manual.
Deep Sea Electronics Ltd
Tel: +44 (0)1723 890099
Email: sales@deepseaelectronics.com
Web: www.deepseaelectronics.com
Deep Sea Electronics Inc
Tel: +1 (815) 316-8706
Fax: +1 (815) 316-8708
Email: USAsales@deepseaelectronics.com
Web: www.deepseaelectronics.com
REQUIREMENTS FOR UL CERTIFICATION
Screw Terminal Tightening Torque
• Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5 mm²).
• Conductor protection must be provided in accordance with NFPA 70, Article 240
• Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least ¼” (6 mm) separation from the generator and mains connected circuit
conductors unless all conductors are rated 600 V or greater.
• Must be connected through UL Listed or Recognized isolating current transformers with the secondary rating of 5 A max.
• Must be connected to communication circuits of UL Listed equipment
• Suitable for use in type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC)
• Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be install in an unventilated or filtered ventilation
enclosure to maintain a pollution degree 2 environment.
• -22 ºF to +158 ºF (-30 ºC to +70 ºC)
• -40 ºF to +176 ºF (-40 ºC to +80 ºC)