Input Sources
0
User Configured
17
Mains Load Inhibit
41
Alternative Configuration 2
1
Remote Start on Load
18
RESERVED
42
Alternative Configuration 3
2
RESERVED
19
External Panel Lock
43
Emergency Stop
3
Auto Start Inhibit
20
Auxiliary Mains Fail
44
RESERVED
4
Lamp Test
21
Oil Pressure Switch
45
Maintenance Reset Oil
5
Alarm Mute
22
Coolant Temperature Switch
46
Maintenance Reset Air
6
Alarm Reset
23
RESERVED
47
Maintenance Reset Fuel
7
RESERVED
24
Simulate Mains Available
48
RESERVED
8
Simulate Start Button
25
Remote Start Off Load
49
RESERVED
9
Simulate Stop Button
26-30
RESERVED
50
DPF Auto Regen Inhibit
10
RESERVED
31
Auto Restore Inhibit
51
DPF Force Regeneration
11
Simulate Auto Button
32
RESERVED
52
DPF Regeneration
Interlock
12
RESERVED
33
Low Fuel Level Switch
53
Water in Fuel
13
Close Generator
Open Mains
34
Smoke Limiting
54
Fuel Bund Level High
14
Generator Load Inhibit
35-38
RESERVED
55
Fan Speed Low
15
RESERVED
39
Main Configuration
56
Low Coolant Level Switch
16
Close Mains
Open Generator
40
Alternative Configuration 1
57
Wait To Start
Output Sources
0
Not Used
46
Mains Low Frequency
92
RESERVED
1
Air Flap Relay
47
Mains Low Voltage
93
RESERVED
2
Audible Alarm
48
Oil Pressure Sensor Open Circuit
94
RESERVED
3
Battery High Volts Warning
49
Open Generator Output
95
Over Speed Overshoot Alarm
4
Battery Low Volts Warning
50
Open Generator Output Pulse
96
Over Frequency Overshoot Alarm
5
CAN ECU Data Fail
51
Open Mains Output
97
Display Heater Fitted and Active
6
ECU (ECM) Warning
52
Open Mains Output Pulse
98
RESERVED
7
ECU (ECM) Shutdown
53
Over Frequency Shutdown
99
SCR Inducement
8
CAN ECU Power
54
Over Speed Shutdown
100
DEF Level Low
9
CAN ECU Stop
55
Preheat During Preheat Timer
101
DPF Auto Regeneration Inhibit
10
Charge Alternator Shutdown
56
Preheat Until End of Crank
102
DPF Forced Regeneration
11
Charge Alternator Warning
57
Preheat Until End of Safety Timer
103
DPF None Mission State
12
Close Generator Output
58
Preheat Until End of Warming
104
DPF Regeneration in Progress
13
Close Generator Output
Pulse
59
Smoke Limiting
105
DPF Regen Interlock Active
14
Close Mains Output
60
Start Relay
106
DPTC Filter
15
Close Mains Output Pulse
61
Temperature Sensor Open Circuit
107
HEST Active
16
Combined Mains Failure
62
Under Frequency Shutdown
108
Water in Fuel
17
Common Alarm
63
Under Speed Shutdown
109
Fuel Pull in Coil
18
Common Electrical Trip
64
Waiting for Manual Restore
110
Generator at Rest
19
Common Shutdown
65
Flexible Sensor C High Alarm
111
Fuel Tank Bund Level High
20
Common Warning
66
Flexible Sensor C High Pre-Alarm
112
ECU Preheat
21
Cooling Down
67
Flexible Sensor C Low Pre-Alarm
113
Water Heater
22
Digital Input A
68
Flexible Sensor C Low Alarm
114
Water Cooler
23
Digital Input B
69
RESERVED
115
Closed to Gen
24
Digital Input C
70
RESERVED
116
Closed to Mains
25
Digital Input D
71
RESERVED
117
Generator Under Frequency
Warning
26
RESERVED
72
RESERVED
118
Generator Over Frequency
Warning
27
RESERVED
73
Fuel Sensor High Alarm
119
Generator Low Voltage Warning
28
RESERVED
74
Fuel Sensor High Pre-Alarm
120
Generator High Voltage Warning
29
Emergency Stop
75
Fuel Sensor Low Pre-Alarm
121
Main Config Selected
30
Energise to Stop
76
Fuel Sensor Low Alarm
122
Alt Config 1 Selected
31
Fail to Start
77
Delayed Load Output 1
123
Alt Config 2 Selected
32
Fail to Stop
78
Delayed Load Output 2
124
Alt Config 3 Selected
33
Fuel Relay
79
Delayed Load Output 3
125
Flexible Sensor A High Alarm
34
Gas Choke On
80
Delayed Load Output 4
126
Flexible Sensor A High Pre-Alarm
35
Gas Ignition
81
Air Filter Maintenance
127
Flexible Sensor A Low Alarm
36
Generator Available
82
Oil Filter Maintenance
128
Flexible Sensor A Low Pre-Alarm
37
Generator High Voltage
Alarm
83
Fuel Filter Maintenance
129
Flexible Sensor A Open Circuit
38
Generator Low Voltage
Alarm
84
System in Stop Mode
130
Fan Speed Low
39
kW Overload Alarm
85
System in Auto Mode
131
Fuel Usage Alarm
40
Over Current Immediate
Warning
86
System in Manual Mode
132
Low Coolant Level
41
Delayed Over Current Alarm
87
RESERVED
133
Low Coolant Level Open Circuit
42
High Coolant Temp
Shutdown
88
Analogue Input A (Digital)
134
Waiting To Start
43
Low Oil Pressure Shutdown
89
Analogue Input B (Digital)
135
High Coolant Temp Pre-Alarm
44
Mains High Frequency
90
Analogue Input C (Digital)
45
Mains High Voltage
91
RESERVED
Functionality in DSE4510 MKII & DSE4520 MKII
Functionality in DSE4520 MKII only
TYPICAL WIRING DIAGRAM
DIMENSIONS
PANEL CUTOUT
TERMINALS
140 mm x 113 mm x 43 mm
(5.5” x 4.4” x 1.7”)
118 mm x 92 mm
(4.6” x 3.6”)
Tightening Torque: 0.5 Nm (4.5 lb-in)
Conductor Size: 0.5 mm² to 2.5 mm²
(AWG 20 to AWG 13)
NOTE: A larger version of the typical wiring diagram is included in
the product’s operator manual. Refer to DSE Publication:
057-260 DSE4510 MKII & DSE4520 MKII Operator Manual
NOTE: Terminals 25, 26, 27 & 28 are not fitted to the DSE4510 MKII
053-234 Issue 4
DEEP SEA ELECTRONICS
DSE4510 MKII & DSE4520 MKII Installation Instructions
Applicable to module version 3.0.0 and upwards.
EDITING A PARAMETER
Press the Stop/Reset Mode ( - ) and Auto Mode () buttons together
to enter the editor mode.
Press the Up or Down navigation buttons to cycle through the front
panel editor in increments of 100.
Press the Manual/Start Mode ( + ) or Stop/Reset Mode ( - ) buttons to
cycle through the front panel editor in increments of 1.
When viewing the parameter to be edited, press the Auto Mode () button
and the value begins to flash.
Press the Manual/Start Mode ( + ) or Stop/Reset Mode ( - ) navigation
buttons to adjust the value to the required setting.
Press the Auto Mode () button to save the current value, the value
ceases flashing.
Press and hold the Auto Mode () button to save and exit the editor, the
configuration icon is removed from the display.
NOTE: Pressing and holding the Manual/Start Mode ( + ) or
Stop/Reset Mode ( - ) buttons will give auto-repeat functionality.
NOTE: More comprehensive module configuration is possible via PC
configuration software. For further details of module configuration, refer
to DSE Publication: 057-258 DSE4510 MKII & DSE4520 MKII
Configuration Suite PC Software Manual.
Deep Sea Electronics Ltd
Tel: +44 (0)1723 890099
Email: sales@deepseaelectronics.com
Web: www.deepseaelectronics.com
Deep Sea Electronics Inc
Tel: +1 (815) 316-8706
Fax: +1 (815) 316-8708
Email: USAsales@deepseaelectronics.com
Web: www.deepseaelectronics.com
REQUIREMENTS FOR UL CERTIFICATION
Specification
Description
Screw Terminal Tightening Torque
4.5 lb-in (0.5 Nm)
Conductors
Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5 mm²).
Conductor protection must be provided in accordance with NFPA 70, Article 240
Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit.
The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least ¼” (6 mm) separation from the generator and mains connected circuit
conductors unless all conductors are rated 600 V or greater.
Current Inputs
Must be connected through UL Listed or Recognized isolating current transformers with the secondary rating of 5 A max.
Communication Circuits
Must be connected to communication circuits of UL Listed equipment
DC Output Pilot Duty
0.5 A
Mounting
Suitable for use in type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC)
Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be install in an unventilated or filtered ventilation
enclosure to maintain a pollution degree 2 environment.
Operating Temperature
-22 ºF to +158 ºF (-30 ºC to +70 ºC)
Storage Temperature
-40 ºF to +176 ºF (-40 ºC to +80 ºC)
DSE4510 MKII &
DSE4520 MKII

Related product manuals