4.2.1 STATUS
NOTE: Press the Instrumentation Scroll buttons on the Status Page to view other
Configurable Status Screens if configured. For further details of module configuration, refer to
DSE Publication: 057-238 DSE8610 MKII Configuration Suite PC Software Manual.
This is the ‘home’ page, the page that is displayed when no other page has been selected, and the
page that is automatically displayed after a period of inactivity (LCD Page Timer) of the module
control buttons.
This page changes with the action of the controller for example when the generator is running and
available:
Factory setting of Status screen showing engine stopped...
Generator at Rest
Stop Mode
4.2.1.1 GENERATOR LOCKED OUT
Generator Locked Out indicates that the Generator cannot be
started due to an active Shutdown or Electrical Trip Alarm on the
module. Press the Next or Previous Page button to
scroll
to the alarms page to investigate. Press the Stop/Reset Mode button to clear the alarm, if the
alarm does not clear the fault is still active.
4.2.1.2 WAITING FOR GENERATOR
NOTE: For further details of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
Waiting For Generator indicates that the Generator has started
but has not reached the required Loading Voltage and or Loading
Frequency as set in the module’s configuration. Press the
Next or Previous Page buttons to scroll to the Generator
page to check to see if the generator voltage and frequency is higher than the configured Loading
Voltage and Loading Frequency.