Document Edition 4.1 Page 11 of 41
C06 Receive overrun
C07 CRC error
C08 MSTP pass token timeout
C09 Out of Sole Master
C10 Invalid state
C11 Invalid frame
C12 Minimum Token cycle time (ms)
C13 Maximum Token cycle time (ms)
C14 Average Token cycle time (ms)
S03 COV subscription failure
System Log (AV35)
The Description field in this object provides a log of the ten most recent events from the least to the
most recent. If the time and date were previously set then the event time can also be determined. Each
log entry has the format [dd/mm/yy hh:mm:ss ***] where *** is the event code. Each event type is
specified by a letter, (H- Hardware, C- Communication, S-Service or O-Other) which is followed by a
two-digit code. For example, 02/05/06 10:12:47 S04. The PresentValue indicates how many items
are in the log.
Code Description
H01 EEPROM communication failure
H02 RTC communication failure
H03 LCD communication failure
H04 Reset
H05 Flash programming
H06 Flash failure
H07 Input failure
H08 I2C communication failure
H09 Humidity sensor failure
C01 Communication overflow
C02 Buffer unavailable
C03 Into Sole Master
C04 DNA conflict
C05 MAC address conflict
S01 Communication disabled
S02 Communication enabled
S03 COV subscription failure
S04 TimeSync received
S05 Database cleared
S06 Speed Changed
R00-07 MS/TP state machine lockup
R10-15 MS/TP timeout lockup
R21 BACnet application processing error
R22 Object execution error
R23 UI manager error
O00 Other