Chapter 5 Parameters|VFD-S Series
Revision August 2006, SE08, SW V2.61 5-9
Group 7 Motor Parameters
Pr. Explanation Settings
Factory
Setting
NOTE
7-00 Motor Rated Current d30 to d120% d85
7-01
Motor No-Load Current
d0 to d90% d50
7-02
Torque Compensation
d0 to d10 d1
7-03 Slip Compensation d0.0 to d10.0 d0.0
Group 8 Special Parameters
Pr. Explanation Settings
Factory
Setting
NOTE
8-00 DC Braking Voltage Level d0 to d30% d0
8-01 DC Braking Time during Start-Up d0.0 to d60.0 Sec d0.0
8-02 DC Braking time during Stopping d0.0 to d60.0 Sec d0.0
8-03 Start-Point for DC Braking d0.0 to d400 Hz d0.0
d0: Operation stops after
Momentary Power Loss
d1: Operation continues after
momentary power loss, speed
search starts with the Master
Frequency reference value
8-04
Momentary Power Loss Operation
Selection
d2: Operation continues after
momentary power loss, speed
search starts with the minimum
frequency
d0
8-05 Maximum Allowable Power Loss Time d0.3 to d5.0 Sec d2.0
8-06 B.B. Time for Speed Search d0.3 to d5.0 Sec d0.5
8-07 Current Limit for Speed Search d30 to d200% d150
8-08 Skip Frequency 1 Upper Limit d0.0 to d400 Hz d0.0
8-09 Skip Frequency 1 Lower Limit d0.0 to d400 Hz d0.0
8-10 Skip Frequency 2 Upper Limit d0.0 to d400 Hz d0.0
8-11 Skip Frequency 2 Lower Limit d0.0 to d400 Hz d0.0
8-12 Skip Frequency 3 Upper Limit d0.0 to d400 Hz d0.0
8-13 Skip Frequency 3 Lower Limit d0.0 to d400 Hz d0.0
8-14 Auto Restart After Fault d0 to d10 d0
d0: Enable
d1: Disable
8-15 AVR Function
d2: Disable when deceleration
d2
115V/230V series: d350 to d450V d380
8-16
Software Braking Level
460V series: d700 to d900V d760
8-17 DC Braking Lower Bound Limit d0.0 to d400 Hz d0.0
Group 9 Communication Parameters