OFF state. shielded cable is grounded.
2. Check if the start and end of the network cable
are both connected with a 121Ω terminal
resistor.
3. Check if all the node devices run at the same
baud rate on the network.
19FB
The sending registers exceed the
range.
Revise the
time to synchronize (suggested to use a
longer time).
- V
19FC
The receiving registers exceed the
Revise the
time to synchronize (suggested to use a
longer time).
- V
2001
Not using the FCOMP card or not in the
right mode for the ASDA-A2 while using
the CANopen communication
instruction.
1. Use the FCOMP card in the function card slot to
check if the operation mode is correct.
2. Check the syntax error step in the program.
Modify and compile the program and then
download the program again.
SM0 V
2003
The device used in the program
exceeds the device range.
Check the syntax error step in the program. Modify
and compile the program and then download the
program again.
SM0 V
200B
The operand n or the other constant
operands K/H exceed the range.
SM0 V
200D
The binary to binary-coded decimal
SM0 V
The string does not end with 00.
Incorrect division operation
2013
The value exceeds the range of values
that can be represented by the floating-
SM0 V
2014
The task designated by the TKON or
YKOFF instruction is incorrect or
exceeds the range.
SM0 V
2017
The instruction BREAK is written
outside of the FOR-NEXT loop.
SM0 V
2027
No such position planning table number
or the format is incorrect.
1. Check the syntax error step in the program.
Modify and compile the program and then
download the program again.
2. Check the settings of the position planning table.
SM0 V
2028
High speed output instruction is being
executed. Only one instruction can be
executed at a time.
Refer to SR28 for the record of the axis number
and rearrange the output control procedures.
-
V
2030
During the execution of CSFO
instruction, the output frequency
exceeds the upper limit.
Modify the ratio of input / output frequency or lower
the inut frequency value.
-
V
2031
During the execution of CSFO
instruciotn, when the output frequency
is set to 0, but even after 2 seconds, the
output is still not complete.
-
V
6004 The IP address filter is set incorrectly.
Set the Ethernet parameter for the CPU module in
SM1108 X
RJ45 port is not connected.