Chapter 3 Parallel Application Introductions Parallel Control Solution
21
3-2 Parallel Setup Steps
3-2-1 C2000 Series Settings
The following is the setting process and descriptions of C2000 series parallel connection, re-power
the drive after completing the set up.
3-2-1-1 C2000 Series Tuning
Control and communication parameters can be set on the master drive
Motor and protection parameters must be identical on both the master and slave drives
Currently, only speed mode (Pr.00-10=0) is supported
3-2-1-2 Master Drive Parameter Setting
1. Set Pr.00-02 = 10 (Parameter reset).
2. Set motor parameters in the Parameter Group 05.
3. Set Pr.00-62 = 1 (Master unit).
4. Check Pr.00-63 (Fiber communication card firmware version).
5. Set Pr.00-64 = 8 (Keypad setting: bit3 = 1, Parallel start).
6. Set Pr.00-11 according to the required mode (Currently supports IMVF and PM Sensorless).
7. Set Pr.00-17 carrier frequency (less than 6 kHz).
8. Set Pr.11-00 = 9.
9. Set Pr.10-53 = 1 (Only required for PM Sensorless).
10. Set parameters for Group 10 and Group 11.
11. Set Pr.00-04 to obtain the motor information: Pr.00-04=73 (output current), 74 (output power)
and 75 (output torque).
3-2-1-3 Slave Side Parameter Setting:
1. Set Pr.00-02 = 10 (Reset parameters).
2. Set motor parameters in Parameter Group 05.
3. Set Pr.00-62 = 2 (Slave unit).
4. Check Pr.00-63 (Fiber communication card firmware version).
5. Set Pr.00-64 = 8 (bit3 = 1, Parallel start).
6. Set Pr.01-34 = 2 (minimum frequency)
7. Set Pr.00-11 according to the required mode (Currently supports IMVF and PM Sensorless).
8. Set Pr.00-17 to match the master drive’s setting value.
9. Set Pr.00-20 = 9.
10. Set Pr.00-21 = 6.
11. Set Pr.11-00 = 9.
12. Set Pr.10-53 = 0.
13. Set parameters for Group 10 and Group 11.