DOP-110IS
High color Wide screen ‧‧
User-friendly
No.18, Xinglong Rd., Taoyuan City
33068, Taiwan
Instruction Sheet
(1) General precautions
Thank you for purchasing this product. This DOP-110IS instruction sheet provides information for the
DOP-110IS series HMI. Before using this product, read through this instruction sheet carefully to ensure
the correct use of the product. Keep this sheet handy for quick reference whenever needed. Before
finishing reading this sheet, follow the instructions below:
Install the product in an indoor location, which is free of vapor and corrosive and inflammable gas.
Refer to the wiring diagram when connecting the wires.
Ensure this product is correctly grounded. The grounding method must comply with the national
electrical standard guidelines (refer to NFPA 70: National Electrical Code, 2005 Ed.).
Do not disassemble the HMI or change the wiring when power is on.
Do not touch the power supply when power is on, or it may cause electric shock.
When the HMI displays a low power notification and requires a battery change, contact Delta or
local distributors for the replacement. Do not change the batteries by yourself.
This product can be used with other industrial automation equipment. Read through this sheet
carefully and install the product according to the instructions to avoid danger.
Cleaning method: use a dry cloth to clean the product.
This product must be used at an altitude below 2,000 m (6561.68 ft).
If the equipment is used in a manner not specified by the manufacturer, the protection function
provided by the equipment may be impaired.
For repair and maintenance, contact Delta Electronics, Inc. Address: No.18, Xinglong Rd.,
Taoyuan City, Taiwan. TEL: +886-3-3626301.
If you have any inquiry during operation, contact our local distributors or Delta Customer Service Center.
The instruction sheet may be revised without prior notice. Contact our distributors or download the latest
version from the Delta website (http://www.deltaww.com.tw/ia).
(2) Communication port pin assignment
DOP-110IS COM1
COM Port Pin
MODE1
RS-232
1 -
2 RXD
3 TXD
4 -
5 GND
6 -
7 RTS
8 CTS
9 -
DOP-110IS COM2
COM Port Pin
MODE1 MODE2 MODE3
RS-232 RS-422 RS-485
1 - TXD+ D+
2 RXD - -
3 TXD - -
4 - RXD+ -
5 GND GND GND
6 - TXD- D-
7 RTS - -
8 CTS - -
9 - RXD- -
Note:
1. The mark “-” means connection is not required.
2. To use COM2 for flow control through RS-232 (RTS and CTS signals), COM3 port is not operable.
DOP-110IS COM3
COM Port Pin
MODE1 MODE2 MODE3
RS-232 RS-422 RS-485
1 - TXD+ D+
2 RXD - -
3 TXD - -
4 - RXD+ -
5 GND GND GND
6 - TXD- D-
7 - - -
8 - - -
9 - RXD- -
Note: the mark “-” means connection is not required.
DOP-110IS Ethernet interface (LAN)
Ethernet interface Pin
Contact
Ethernet
1 TX+
2 TX-
3 RX+
4 -
5 -
6 RX-
7 -
8 -
Note: the mark “-” means connection is not required.
(3) Description of each part
DOP-110IS (front view)
A
A Operation / display area
DOP-110IS (rear view)
AC D E
F
GBHI
SLA VE
HO S T
AU DI O
OUT
A Power input connector F Ethernet interface (LAN)
B COM2 (supports communication indicator) G USB Slave
C COM3 (supports communication indicator) H USB Host
D COM1 I Memory card slot
E Audio output interface - -
(4) Mounting dimensions
DOP-110IS
272.6(10.73")
200.6(7.09")
261.3 (10.29" )
+1.0
.0
0
+0.04".
.0
0
T
54(33.62")
10.4
Note:
T = 1.6 mm – 6 mm (0.063" - 0.24")
(5) Installation and wiring
Precautions:
Mount the HMI according to the illustration below. Incorrect installation direction may result in
malfunction.
To ensure the HMI is well ventilated, make sure there is sufficient space between the HMI and the
adjacent objects or walls.
This product should be used on a case / platform which conforms to enclosure Type 4X standard
(for indoor use only).
The maximum panel thickness for mounting must be no greater than 5 mm (0.2 inches).
Use copper wires.
Installation diagram:
Step 1:
Put the waterproof gasket onto the HMI and
then insert the HMI into the panel cutout.
Step 2:
Place the fasteners into the slots and tighten the
screws until reaching the panel cutouts.
Unit: mm (inches)
Question and Answer IconNeed help?

Do you have a question about the Delta DOP-110IS and is the answer not in the manual?

Delta DOP-110IS Specifications

General IconGeneral
Display TypeTFT LCD
Resolution1024 x 600 pixels
Touch TechnologyResistive
RAM128 MB
ROM256MB
Ethernet1 x 10/100 Mbps
SD Card SlotYes
Power Input24 VDC
Brightness350 cd/m²
Protection RatingIP65 (front panel)
Display Size10.1 inches
Serial Ports2 x COM ports
Operating Temperature0°C to 50°C
Storage Temperature-20°C to 60°C
Humidity10% to 90% (non-condensing)

Summary

General Precautions and Safety

Safety and Usage Guidelines

Provides essential safety instructions and general precautions for using the DOP-110IS HMI correctly.

Communication Port Pin Assignments

COM1 Port Pin Assignment

Details pin assignment for COM1 port using RS-232 communication.

COM3 Port Pin Assignment

Details pin assignment for COM3 port using RS-232, RS-422, and RS-485.

Ethernet Interface (LAN) Pin Assignment

Details pin assignment for the Ethernet interface (LAN) port.

COM2 Port Pin Assignment

Details pin assignment for COM2 port using RS-232, RS-422, and RS-485.

Product Description and Views

Front View Description

Identifies the operational display area and other components on the front of the HMI.

Rear View Description

Identifies connectors and components located on the rear of the HMI.

Mounting and Installation

Mounting Dimensions

Provides the physical dimensions required for mounting the HMI unit.

Installation and Wiring Precautions

Details crucial steps and precautions for proper installation and wiring.

Wiring Instructions

Provides guidance on wire gauge, stripping length, torque, and temperature rating for wiring.

Hardware Specifications

Model and Cooling

Specifies the model number, cooling method, and approvals.

Panel and Operation Specifications

Details panel type, resolution, backlight, display range, and brightness.

Performance Specifications

Lists CPU, memory, touchscreen, buzzer, and audio output capabilities.

Connectivity Specifications

Details specifications for network interface, USB, and serial communication ports.

Related product manuals