DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming 
 
Special 
register 
Function 
D1120 
COM2 (RS-485) communication protocol. Refer to the following table in 
point 4 for protocol setting. 
D1121 
COM1 (RS-232) and COM2 (RS-485) PLC communication address when 
PLC is slave. 
D1122  COM2 (RS-485) Residual number of words of transmitting data. 
D1123 
When M1263 is OFF, the value in D1123 indicates the remaining bytes of 
data to be received.   
When M1263 is ON, the value in D1123 indicates the bytes of data that 
are received. 
D1124 
COM2 (RS-485) Definition of start character (STX) Refer to the following 
table in point 3 for the setting. 
  S
upported communication instruction: RS 
D1125 
COM2 (RS-485) Definition of first ending character (ETX1) Refer to the 
following table in point 3 for the setting. 
Supported communication instruction: R
S 
D1126 
COM2 (RS-485) Definition of second ending character (ETX2) Refer to 
the following table in point 3 for the setting. 
Supported communication instruction: R
S 
D1129 
COM2 (RS-485) Communication time-out setting (unit: ms). If users set 
up time-out value in D1129 and the data receiving time exceeds the 
time-out value, M1129 will be set ON and the error code K1 will be stored 
in D1130. M1129 has to be reset manually when time-out status is 
cleared. 
D1130 
COM2 (RS-485) Error code returning from Modbus. RS instruction is not 
included. 
Supported communication instructions: M
ODRD / MODWR / FWD / REV 
/ STOP / RDST / RSTEF / MODRW 
D1168 
When M1263 is ON, the value in D1168 indicates a specific end word to 
be seen as an interrupt request; unit: ms. It is suggested to set this value 
shorter than what the timeout value is set in D1129.   
When M1263 is OFF, and the received data is low-byte of a specific 
word, the interrupt (I150) is triggered.   
Supported communication instruction: R
S 
D1256~D1295 
For COM2 RS-485 MODRW instruction. D1256~D1295 store the sent 
data of MODRW instruction. When MODRW instruction sends out data,