EasyManua.ls Logo

Delta DVP-SX2 - C.4.3 Additional Remarks on High-speed Instructions

Delta DVP-SX2
1006 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming
C-30
Classification API
Mnemonic
PULSE
Function
16 bits
32 bits
281
FAND=
S
1
S
2
282
FAND>
S
1
S
2
283
FAND<
S
1
S
2
284
FAND<>
S
1
≠ S
2
285
FAND<=
S
1
S
2
286
FAND>=
S
1
S
2
287
FOR=
S
1
S
2
288
FOR>
S
1
S
2
289
FOR<
S
1
S
2
290
FOR<>
S
1
≠ S
2
291
FOR<=
S
1
S
2
292
FOR>=
S
1
S
2
C.4.3 Additional Remarks on High-speed Instructions
1. TP only supports the high-speed inputs X0 and X1 (10KHz). (Please refer to section 2.12 for
more information.) TP04P-08TP1R does not support high-speed inputs (only supports up to
500HZ).
2. TP only supports the software counters C235 and C236. The corresponding high-speed
interrupts are I010 and I020. (Please refer to the explanations of API53 and API55 for more
information.)
3. TP onlyt supports the hardware counter C251. The corresponding high-speed interrupt is I010.
There is only one hardware comparator. (Please refer to the explanations of API53 and API55
for more information.)