- 3 -
Load cell module Voltage output
Average value filter Setting range: K1 to K100
Isolation method
500 VAC between digital circuits and Ground
500 VAC between analog circuits and Ground
500 VAC between analog circuits and digital circuits
Series connection to
DVP-PLC MPU
Connectable to the left side of MPU, numbered from 100 to
107 according to the position of module from the closest to
farthest to MPU.
Operation / storage
temperature
Operation: 0 to 55°C (temp.), 5 to 95% (humidity), pollution
degree 2
Storage: -25 to 70°C (temp.), 5 to 95% (humidity)
Vibration / shock immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Complying with DIN1319-1, the tolerance of measured value should be ≤ 0.05% under 20°C
+ 10K temperature range
.
When the corrected ambient temperature and the actual temperature have a difference of
more than 10°C, it is suggested that you re-correct it.
Control Register
CR# Add. Attrib. Register name Explanation
#0 H1000 O R Model name
Set up by the system:
DVP01LC-SL model code = H’4106
#1 H1001 O R Firmware version
Displaying the current firmware version in
hex.
#2 H1002 O R/W Eigenvalue
Mode 0 (H’0000): 1 mV/V
Mode 1 (H’0001): 2 mV/V, default
Mode 2 (H’0002): 4 mV/V
Mode 3 (H’0003): 6 mV/V
#3 H1003 O R/W
Reaction time for
measurement
Mode 0 (H’0000): 2 ms
Mode 1 (H’0001): 10 ms
Mode 2 (H’0002): 20 ms
Mode 3 (H’0003): 40 ms
Mode 4 (H’0004): 80 ms, default
Mode 5 (H’0005): 200 ms
Mode 6 (H’0006): 380 ms
#6 H1006 X R/W Tare gotten from CH1
Reading the present average value as
tare
bit0: CH1
#7 H1007 O R/W Gross/Net weight
Taking the present weight as the gross
weight (K0) or the net weight (K1).
#8 H1008 O R/W
Gross weight from CH1
(Low word)
Users can input the value or use the
instruction to read the gross weight.
Default: 0
#9 H1009 O R/W
Gross weight from CH1
(High word)
#10 H100A O R/W
Average number of times
gotten from CH1
Default: K10; Range: K1~K100
If the setting value exceeds the range, it
will be automatically changed to K1 or
K100.
#12 H100C X R
Weight gotten from CH1
(Low word)
Displaying the weight.
Default: K0
#13 H100D X R
Weight gotten from CH1
(High word)
Displaying the weight.
Default: K0