DVP-ES3 Series Operation Manual
5-36
_5
04PT
06PT
Attrib.
Register content
Description
25 X R
Present temperature
measured at CH6
26 O R/W
Mode 4 (H’0004):
0~300Ω. Temperature
display decimal digit
changes
In mode 4 (0~300Ω), temperature display decimal changes (0: 1
digit after the decimal place/ 1: 2 digits after the decimal place).
Default= H0
27 O R/W Temperature unit setting
Select the temperature unit (Celsius °C / Fahrenheit °F).
Default = H’0(°C)
28 28 O R/W
Adjusted offset value of
CH1
Adjusted offset value, range K-1000 ~ K1000. Default = K0
Measured Value = Original Value Adjusted offset value
Unit Setup:
● DVP04PT-E2: CR#7
● DVP06PT-E2: CR#27
29 29 O R/W
Adjusted offset value of
CH2
30 30 O R/W
Adjusted offset value of
CH3
31 31 O R/W
Adjusted offset value of
CH4
32 O R/W
Adjusted offset value of
CH5
33 O R/W
Adjusted offset value of
CH6
40 40 O R/W
Function: Set value
changing prohibited
Prohibit set value changing, b0~b5 corresponds to CH1 ~ CH6.
Default =H’0000
41 41 X R/W
Function: Save all the set
values
Save all the set values. Default =H’0000
43 43 X R Error status
Register for storing all error status. See the table of error status
for more information.
100 100 O R/W
Function: Enable/Disable
limit detection
Upper and lower bound detection, b0~b5 corresponds to CH1 ~
CH6 (0: Disable/ 1: Enable). Default= H’0000.
101 101 X R/W
Upper and lower bound
status
Display the upper and lower bound status (0: Not Exceeding; 1:
Exceeding upper and lower bound value), b0~b5 corresponds to
CH1 ~ CH6 lower bound, b8~b13 corresponds to CH1 ~ CH6
upper bound.
Default =H’0000
102 102 O R/W
Set value of CH1 upper
bound
Set upper bound value. Default = K32000.
103 103 O R/W
Set value of CH2 upper
bound
104 104 O R/W
Set value of CH3 upper
bound
105 105 O R/W
Set value of CH4 upper
bound
106 O R/W
Set value of CH5 upper
bound
107 O R/W
Set value of CH6 upper
bound
108 108 O R/W
Set value of CH1 lower
bound
Set lower bound value. Default = K-32000.
109 109 O R/W
Set value of CH2 lower
bound
110 110 O R/W
Set value of CH3 lower