DVP-ES3 Series Operation Manual
3) Note the limitation on the length of the CANopen network. The transmission distance of the CANopen
network depends on the transmission rate of the CANopen network. The following table shows the
relation between the transmission rate and the maximum communication distance.
Transmission rate
20K 50K 125K 250K 500K 1M
Maximum
communication distance
(meters)
2500 1000 500 250 100 25
4) The list below shows the Delta network products for the CANopen network.
AS332T-A
AS332P-A
AS324MT-A
AS320T-B
AS320P-B
AS300N-A
The AS300 series PLC can function as the
CANopen master or slave when you install an
AS-FCOPM function card. The AS-FCOPM is
equipped with a 120 ohm resistor controlled
by a switch.
AS228T-A
AS228P-A
AS228R-A
AS218TX-A
AS218PX-A
AS218RX-A
AS200 Series PLC is built with CAN
communication port. The CAN port conforms
to the basic communication protocol
CANopen DS301. It supports master and
slave modes. The CAN communication
terminal is equipped with a 120 Ω resistor.
You can use a short circuit to use this resistor.
DVP32ES300T
DVP32ES311T
DVP48ES300R
DVP48ES300T
DVP64ES300R
DVP64ES300T
DVP80ES300R
The DVP-ES3 Series PLC has a built-in CAN
interface. It can function as the CANopen
master or slave.
DVP32ES200RC
DVP32ES200TC
The DVP-ES2-C series PLC has a built-in
CAN interface. It can function as the
CANopen master or slave.
DVPCOPM-SL
DVPCOPM-SL is a module connected to the
left side of an S series PLC. It can function as
the CANopen master or slave. The PLCs that
you can connect to the DVPCOPM-SL are the
DVP-28SV, DVP-28SV2, DVP-SX2,
DVP-SA2, and DVP-EH2-L.