26
Inverter model Recommended AC branch protection
 E6 -TL -US  2-pole, 30 A 240 Vac
 E8 -TL -US 
2-pole, 40 A 240 Vac
4.3  AC circuit breaker requirements
Please note that there is an exception to the requirement of a dedicated circuit breaker in the buil-
ding circuit panel for each inverter if there exists a dedicated PV system AC subpanel that is used 
to combine multiple inverters. In this case, only one breaker at the main building service panel 
should be installed for a multiple inverter installation utilizing a dedicated PV system AC subpanel.
A dedicated circuit breaker in the building circuit panel is required for each Delta  E series  inverter 
that is installed. There should be a circuit breaker or fuse to protect each AC line, L1 and L2. The 
circuit breaker should be able to handle the rated maximum output voltage and current of the 
inverter. Please refer to the table below to determine the appropriate circuit breaker size to avoid 
potential re hazards. The National Electrical Code (NEC), ANSI/NFPA 70 or applicable local elec-
trical codes must be folllowed when determining maximum branch-circuit over-current protection 
requirements.
4.4  Grounding electrode conductor (GET) 
Per NEC 690.47, a Grounding Electrode Conductor must be installed, and the GET conductor 
must be sized in accordance with NEC article 250.166. The GET conductor should be terminated 
at the GET screw terminal inside the wiring box compartment.
4.5  Lightning and surge protection
Delta  E series  NA inverters are designed and certied to meet stringent UL 1741 / IEEE 1547 
and ANSI/ IEEE 62.41/62.42 AC lighting and surge requirements; however, every PV installation is 
unique, thus additional external UL/NEC AC and DC surge protection and solid grounding practice 
is recommended
4.6  Multiple inverters
Multiple Delta  E series  inverters are permitted at a common location if all applicable NEC, state, 
local building codes and local utility commissioning guidelines are met. In addition, each inverter 
should have its own dedicated AC branch protection circuit breaker and a dedicated PV string/
array, not to exceed the inverter’s ratings.
Table 4:  Recommended AC branch protection for Delta E series solar inverters
There are a large number of PV module string combinations that will oer optimal performance 
from either the E6-TL-US and E8-TL-US inverters 
thanks to its wide full power MPP range (50 V – 480 V)
4.7  PV string considerations