39
4.8.9  Inverter AC output wire connections
–   Read all of the instructions, cautions, and warnings for the  
  Delta  E series  Inverter, associated PV array documentation.
  Lisez toutes les instructions, rubriques Prudence et Avertisse 
  ment de l’onduleur Delta  E series , ainsi que la documentation  
  sur le panneau photovoltaïque associé.
–   Installation and commissioning must be performed by a   
  licensed electrician in accordance with local, state, and    
  National Electrical Code ANSI/NFPA 70 requirements.
 
  L’installation et la mise en service doivent être eectuées par  
  un électricien autorisé conformément aux exigences locales et  
  nationales ainsi qu’au National Electrical Code ANSI/NFPA 70.
–   Ensure no live voltages are present on PV input and AC 
  output circuits, and verify that the DC disconnect, AC 
  disconnect, and dedicated AC branch circuit breaker are in  
  the “OFF” position, before inverter installation.
  Assurez-vous qu’aucune tension directe n’est présente sur les  
  circuits photovoltaïques d’entrée et de sortie du CA,    
  vériez que le CC et le CA sont déconnectés, et que le    
  disjoncteur de dérivation dédié est sur position “OFF”, avant  
  de procéder à l’installation de l’onduleur.
–   Verify that dedicated 2-pole 240 Vac / 208 Vac circuit 
  breaker in the building electrical service panel is turned-o.
  Vériez que le disjoncteur à 2 circuits de 240 Vca / 208 Vca du  
  tableau d’alimentation électrique du bâtiment est mis hors  
 tension.
WARNING!
AVERTISSEMENT!
INFORMATION!
INFORMATIONS!
All screw terminals accept solid or stranded copper DC:12 – 8 
AWG wire,AC: 10 – 6 AWG wire. 
Toutes les bornes à vis n‘acceptent que les ls de cuivre rigides 
ou souples de DC:12 – 8 AWG ,AC: 10 – 6 AWG. I
.
The AC output (neutral) is not bonded to ground in the inverter.
La sortie de courant alternatif (neutre) n’est   pas lié à la masse de 
l‘onduleur.
INFORMATION!
INFORMATIONS!