Chapter 7 InsightPower SNMP IPv6 for rSTS
29
LogM Report monthly log.
[Index | Month] [1-200]
<List of monthly log>
Setting
SetTime Set the present time.
hh:mm:ss
[MM/DD/YYYY]
[Message]
SetDate Set the present date.
MM/DD/YYYY [Message]
SetPrefer Set the preferred source.
1 or 2 [Message]
SetDevID Set the unit's device ID.
<20 characters>
alphanumeric only
[Message]
SetVtp2s
Set the primary to secondary
trip voltage.
165.0 ~ 175.0 [Message]
SetVts2p
Set the secondary to primary
trip voltage.
165.0 ~ 175.0 [Message]
SetVbp2s
Set the primary to secondary
brownout voltage.
180.0 ~ 264.0 [Message]
SetVbs2p
Set the secondary to primary
brownout voltage.
180.0 ~ 264.0 [Message]
SetTdp2s
Set the recovery time of
transfer from primary to
secondary.
12.0 ~ 1800.0 [Message]
SetTds2p
Set the recovery time of
transfer from secondary to
primary.
12.0 ~ 1800.0 [Message]
SetMvs1
Set the max voltage of
comparing cycles for primary
AC blackout.
30 ~ 50 [Message]
SetMvs2
Set the max voltage of
comparing cycles for
secondary AC blackout.
30 ~ 50 [Message]
SetMts1
Set the max time of comparing
cycles for primary AC blackout.
2.0 ~ 4.0 [Message]
SetMts2
Set the max time of comparing
cycles for secondary AC
blackout.
2.0 ~ 4.0 [Message]