English-18 
Parameter  Explanation  Settings 
Factory 
Setting
Customer
Pr.142 
Second Source of 
Frequency Command
00: Keypad Up/Down 
01: AVI (0-10V) 
02: ACI (4-20mA) 
03: Communication 
04: Keypad potentiometer 
00  
115V/230V  370-450 Vdc  380.0  
460V   740-900 Vdc  760.0  
Pr.143  Software Braking Level
575V 925-1075 Vdc  950.0  
Pr.144 
Total operation time 
(Day) 
Read Only 
Pr.145 
Total operation time 
(Minutes) 
Read Only 
Pr.146 Line start Lockout 
00: Disable 
01: Enable 
00  
Pr.147 
Decimal Number of 
Accel / Decel Time 
00: One decimal 
01: Two decimals 
00  
Pr.148  Number of Motor Poles 02 to 20  04   
Pr.149 
Gear Ratio for Simple 
Index Function 
4 to 1000  200   
Pr.150 
Index Angle for Simple 
Index Function 
00.0 to 360.0  180.0  
Pr.151 
Deceleration Time for 
Simple Index Function
0.00 to 100.00 sec  0.00   
Pr.152  Skip Frequency Width 0.00 to 400.0Hz  0.00   
Pr.153  Bias Frequency Width 0.00 to 400.0Hz  0.00   
Pr.154 Reserved 
aPr.155 
Compensation 
Coefficient for Motor 
Instability 
0.0: Disable 
0.1 to 5.0 (recommended setting d2.0) 
0.0 
 
aPr.156 
Communication 
Response Delay Time
0 to 200 (x500us)  0 
 
aPr.157 
Communication Mode 
Selection 
0: Delta ASCII 
1: Modbus 
1