Chapter 16 PLC Function ApplicationsC2000 Plus 
 
16-142
Velocity Control 
Special D  Description of Function  Default 
PDO Default 
R/W 
1  2  3  4 
D2001+100*n 
Torque restriction on slave station 
number n   
0   RW 
D2012+100*n 
Target speed of slave station number 
n (rpm)   
0  ●     RW 
D2013+100*n 
Actual speed of slave station number 
n (rpm)   
0  ▲      R 
D2014+100*n 
Error speed of slave station number n 
(rpm)  
0   R 
D2015+100*n 
Acceleration time of slave station 
number n (ms)   
1000  RW 
D2016+100*n 
Deceleration time of slave station 
number n (ms)   
1000  RW 
Torque control   
Special D  Description of Function  Default  
PDO Default 
R/W 
1  2  3  4 
D2017+100*n 
Target torque of slave station number 
n(-100.0% – +100.0%) 
0   ● RW 
D2018+100*n 
Actual torque of slave station number 
n(XX.X%) 
0   ▲ R 
D2019+100*n 
Actual current of slave station number 
n(XX.XA) 
0   R 
Position control   
Special D  Description of Function  Default:  
PDO Default:   
R/W 
1  2  3  4 
D2020+100*n  Target of slave station number n (L)  0 
 ● 
RW 
D2021+100*n  Target of slave station number n (H)  0  RW 
D2022+100*n 
Actual position of slave station 
number n (L) 
0 
 ▲ 
R 
D2023+100*n 
Actual position of slave station 
number n (H) 
0 R 
D2024+100*n 
Speed chart of slave station number n 
(L) 
10000 
 
RW 
D2025+100*n 
Speed chart of slave station number n 
(H) 
0 RW 
Remote I/O 
Special D  Description of Function  Default:  
PDO Default:   
R/W 
1  2  3  4 
D2026+100*n  MI status of slave station number n    0    ▲    R 
D2027+100*n  MO setting of slave station number n    0    ●   RW 
D2028+100*n  AI1 status of slave station number n    0    ▲    R 
D2029+100*n  AI2 status of slave station number n    0    ▲    R 
D2030+100*n  AI3 status of slave station number n    0    ▲    R 
D2031+100*n 
O1 setting of slave station number n  0    ●   RW 
D2032+100*n 
O2 setting of slave station number n  0    ●   RW 
D2033+100*n 