Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-06-24
 
06-49 
Lvx Auto-Reset 
 
 
   
 Default: 0 
 
 
Settings 0: Disabled 
1: Enabled 
 
 
06-50 
Time for Input Phase Loss Detection 
 
 
   
 Default: 0.2 
 
 
Settings 0.00–600.00 sec. 
 
 
06-51 
Capacitance oH Warning Level (Applied to 230V / 460V Models) 
 
 
   
  Default: Depending on the 
model power 
 
 
Settings 0.0–110.0 degree 
 Set the over-heat warning level of the drive’s internal DC bus capacitor. 
 When the setting is less than 10.0 degree, the drive uses its internal capacitor oH warning level. 
 
06-52 
Ripple of Input Phase Loss 
 
 
   
 Default:  
 
 
Settings  230V models: 0.0–160.0 V
DC
 30.0 
 
 
  460V models: 0.0–320.0 V
DC
 60.0 
 
 
  575V models: 0.0–400.0 V
DC
 75.0 
 
 
  690V models: 0.0–480.0 V
DC
 90.0 
 
 
06-53 
Input Phase Loss Detection Action (OrP) 
 
 
   
 Default: 0 
 
 
Settings  0: Fault and ramp to stop 
1: Fault and coast to stop 
 When the drive detects the DC bus ripple exceeds the setting for Pr.06-52, and lasts for the time 
of Pr.06-50 plus 30 seconds, the drive executes the input phase loss protection according to Pr.06-
53.  
 During the time of Pr.06-50 plus 30 seconds, if the DC bus ripple drops lower than the setting for 
Pr.06-52, the Orp protection recalculates.   
 
06-55 
Derating Protection 
 
 
   
 Default: 0 
 
 
Settings  0: Auto-decrease carrier frequency and limit output current 
1: Constant carrier frequency and limit output current   
2: Auto-decrease carrier frequency 
 Refer to Pr.00-01 (Maximum Operation Frequency) for allowable maximum output frequency in 
each control mode.   
 The corresponded carrier frequency lower limit under each control mode:   
  VF, SVC, VFPG, and PM Sensorless:
 Maximum operation frequency (Pr.01-00) × 10 
minimum sampling point limit.