Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-11-4
  Perform the operation test with load based on the inertia after tuning. Run the motor in 
acceleration, deceleration, and steady speed and observe the values. If values between speed 
feedback and speed command are close, steady-state error is small and overshoot is less, then 
this inertia is a better one. 
  If the Iq current command from ASR has high-frequency glitch, then decrease the setting. If the 
response time of sudden loading is too slow, then increase the setting. 
  When using torque mode as the control mode, perform the tuning with speed mode first to see 
if the tuned inertia can work normally. After verifying with speed mode, change the control mode 
to torque mode. 
The base values of induction motor system inertia are listed below:               (Unit: kg-cm
2
)  
HP kW Base value  HP kW Base value  HP kW Base value 
1   0.75  2.3    40   30  202.5    300  220  5139.0 
2   1.5  4.3    50   37  355.5    340   250  5981.0 
3   2.2  8.3    60   45  410.8    375   280  5981.0 
5   3.7  14.8    75   55  494.8    425  315  5981.0 
5 4.0  26.0  100  75 1056.5  475 355 5981.0 
7   5.5  26.0    125   90  1275.3    530  400  5981.0 
10   7.5  35.8    150   110  1900.0    600  450  5981.0 
15  11  74.3  175  132 2150.0  675 500 5981.0 
20  15  95.3  215  160 2800.0  750 560 5981.0 
25   18.5  142.8    250   185  3550.0         
30   22  176.5    270  200  5139.0         
The base value of synchronous motor system inertia is set by Pr.05-38 and the unit is in kg-cm
2
.  
 
11-02 
ASR1 / ASR2 Switch Frequency 
 
 
   
 Default: 7.00 
 
 
Settings 5.00–599.00 Hz 
  Set the low-speed and high-speed ASR switching point in the FOC area. Provides flexibility to 
meet two needs: give a high response in the high-speed region of the estimator switch point, 
and give a lower response in the low-speed region of the estimator switch point. The 
recommended switching point is higher than Pr.10-39. 
  A low setting does not cover Pr.10-39. If the setting is too high, the high-speed range is too 
narrow. 
  If Pr.00-11 = 8 (SynRM sensorless), then the default becomes 10.00 Hz. 
 
11-03 
ASR1 Low-speed Bandwidth 
 
11-04 
ASR2 High-speed Bandwidth 
 
11-05 
Zero-speed Bandwidth 
 
 
   
 Default: 10 
 
 
Settings  1–[(Pr.00-17 carrier frequency) ÷ 40] Hz 
  After estimating inertia and setting Pr.11-00 bit0 = 1 (auto-tuning), you can adjust Pr.11-03, Pr.11-
04 and Pr.11-05 separately by speed response. The larger the setting value, the faster the 
response. Pr.11-02 is the switch frequency between the low-speed / high-speed bandwidth. 
  If Pr.00-11 = 8 (SynRM sensorless), then the upper limit value becomes 30, and the default 
becomes 5.