Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-11-9
3.  Adjust the Pr.11-21 (motor 1) or Pr.11-22 (motor 2) setting to make the output voltage reach 
the motor rated voltage. 
4.  The larger the setting value, the greater the output voltage. 
 
 
11-23 
Flux Weakening Area Speed Response 
 
 
   
 Default: 65 
 
 
Settings 0–150% 
  Control the speed in the flux weakening area. The larger the value, the faster the acceleration / 
deceleration. In normal condition, you do not need to adjust this parameter. 
 
11-24 
APR Gain 
 
 
   
 Default: 5.00 
 
 
Settings  0.00–40.00 Hz (IM) / 0.00–100.00 Hz (PM) 
 Define the Kp gain for the Automatic Position Regulator (APR). The larger the APR proportional 
gain, the higher the position loop response bandwidth.   
 A large APR proportional gain causes a smaller phase margin, further making the motor oscillate 
back and forth. In this case, decrease the APR proportional gain value until the oscillation stops. 
If the APR proportional gain is getting smaller, the motor stiffness is lower when the motor stops. 
 The smaller the APR proportional gain, the lower the motor stiffness when positioning. 
 If increasing APR proportional gain does not meet your application even APR proportional gain is 
much larger than ASR speed bandwidth, adjust ASR speed bandwidth to a suitable value before 
adjusting APR proportional gain. 
 The actual position curve when increasing the APR proportional gain: from A to C (C > B > A). The 
dotted line is the position command, as shown in the diagram below.