Chapter 13 Warning CodesC2000  Plus 
 
ID No.  Display on LCD Keypad  Warning Name  Description 
8 
 
Save error 2   
(SE2) 
Keypad COPY error 2: parameter writing error 
Action and Reset 
Action condition 
“SE2” warning 
occurs when writing the parameters incorrectly at the time you 
copy parameters to the drive. For example, you copy the new firmware version 
with added parameters to the drive with old firmware version. 
Action time  N/A 
Warning setting parameter  N/A 
Reset method  Manual reset 
Reset condition  Immediately reset 
Record  N/A 
Cause  Corrective Actions 
Add new parameters to the new 
firmware version. 
SE2: In this stage, the copied data has been transmitted to the Slave. 
The Slave compares and processes the copied data, and then saves the data 
the Data ROM. 
During the process, the data error (should be attribution error) 
may occur, or the 
data cannot be saved to EEPROM. At this time, the warning 
occurs. 
It is suggested to 
check the status of Data ROM and remove the error causes 
first. 
If you cannot clear the error, please contact Delta. 
Malfunction caused by 
interference 
Verify the wiring and grounding of the main cir
cuit, control circuit and the encoder 
for effective anti-interference performance.