VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-18
Group 9: Communication Parameters
Parameters Explanation Settings
Factory
Setting
09-00 Communication Address 01 to 254 01
00: Baud Rate 4800bps
01: Baud Rate 9600bps
02: Baud Rate 19200bps
09-01 Transmission Speed
03: Baud Rate 38400bps
01
09-02
Transmission Fault
Treatment
00: Warn and keep Operating
01: Warn and Ramp to Stop
02: Warn and Coast to Stop
03: No warning and keep Operating
03
0.0 ~ 60.0 second
09-03 Overtime Detection
0.0: Disable
0.0
00: 7,N,2 (Modbus, ASCII)
01: 7,E,1 (Modbus, ASCII)
02: 7,O,1 (Modbus, ASCII)
03: 8,N,2 (Modbus, RTU)
04: 8,E,1 (Modbus, RTU)
09-04 Communication Protocol
05: 8,O,1 (Modbus, RTU)
00
09-05 HMI Register 1
00 ~ 65535
00
09-06 HMI Register 2
00 ~ 65535
00
09-07 Response Delay Time
00 ~ 200
00