Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-02-15
As long as Pr.02-12 = 9 is set through communications, there is no need to wire any multi-function
terminal to run forward with the second step speed.
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
MI14 MI13 MI12 MI11 MI10 MI9 MI8 MI7 MI6 MI5 MI4 MI3 MI2 MI1
Use Pr.11-42 bit 1 to select whether FWD / REV terminal is controlled by Pr.02-12 bit 0 and
bit 1.
02-13
Multi-Function Output 1 (Relay1)
Default: 11
02-14
Multi-Function Output 2 (Relay2)
Default: 1
02-16
Multi-Function Output 3 (MO1)
Default: 66
02-17
Multi-Function Output 4 (MO2)
02-36
Output Terminal of I/O Extension Card (MO10) or (RA10)
02-37
Output Terminal of I/O Extension Card (MO11) or (RA11)
02-38
Output Terminal of I/O Extension Card (RA12)
02-39
Output Terminal of I/O Extension Card (RA13)
02-40
Output Terminal of I/O Extension Card (RA14)
02-41
Output Terminal of I/O Extension Card (RA15)
02-42
Output Terminal of I/O Extension Card (MO16 Virtual Terminal)
02-43
Output Terminal of I/O Extension Card (MO17 Virtual Terminal)
02-44
Output Terminal of I/O Extension Card (MO18 Virtual Terminal)
02-45
Output Terminal of I/O Extension Card (MO19 Virtual Terminal)
02-46
Output Terminal of I/O Extension Card (MO20 Virtual Terminal)
Default: 0
Settings 0: No function
1: Indication during RUN
2: Operation speed reached
3: Desired frequency reached 1 (Pr.02-22)
4: Desired frequency reached 2 (Pr.02-24)
5: Zero speed (Frequency command)
6: Zero speed including STOP (Frequency command)
7: Over-torque 1 (Pr.06-06–06-08)
8: Over-torque 2 (Pr.06-09–06-11)
9: Drive is ready
10: Low voltage warning (Lv) (Pr.06-00)
11: Malfunction indication
12: Mechanical brake release (Pr.02-32)
13: Overheat warning (Pr.06-15)
14: Software brake signal indication (Pr.07-00)
15: PID feedback error (Pr.08-13, Pr.08-14)