Chapter 12 Description of Parameter SettingsCP2000 
 
 
12.1-06-32 
  When in fire mode, the skip frequency function is not available. 
  When  in  fire  mode,  the  operating  frequency  for  Pr.06-81  cannot  be  larger  than  Pr.01-00 
Maximum Output Frequency. If Pr.06-81 > Pr.01-00, the maximum frequency is automatically set 
to Pr.01-00.