Chapter 13 Warning CodesCP2000 
 
13-14
ID No.  Display on LCD Keypad  Warning Name  Description 
24 
 
Over slip warning 
(oSL) 
Over slip warning. 
By  using  the  maximum  slip  (Pr.10-29)  as  the  base, 
when the drive outputs at constant speed, and the F>H 
or  F<H  exceeds  Pr.07-29  level  and  Pr.07-30  setting 
time, 100% Pr.07-29 = Pr.10-29.   
Action and Reset 
Action level 
When  the  drive  outputs  at  constant  speed,  and  F>H  or  F<H  exceeds  the 
Pr.07-29 level 
Action time  Pr.07-30 
Warning setting parameter 
Pr.07-31=0 Warning 
0: Warn and keep operation 
1: Fault and ramp to stop 
2: Fault and coast to stop 
3: No warning 
Reset method 
When Pr.07-31=0 and when the drive outputs at constant speed, and F>H or 
F<H no longer exceeds the Pr.07-29 level, the oSL warning automatically clears. 
Reset condition  N/A 
Record  N/A 
Cause  Corrective Actions 
Check if the motor parameter is 
correct 
Check the motor parameter. 
The load is too large  Decrease the loading. 
Check if the settings for Pr.07-29, 
Pr.07-30 and Pr.10-29 are properly 
set 
Check the parameter settings for oSL protection. 
 
ID No.  Display on LCD Keypad  Warning Name  Description 
25 
 
Auto tuning   
(tUn) 
Parameter auto-tuning is processing. 
When running auto-tuning, the keypad displays “tUn”. 
Action and Reset 
Action level  When running Pr.05-00 motor parameter auto-tuning, the keypad displays “tUn”. 
Action time  N/A 
Warning setting parameter  N/A 
Reset method 
When  auto-tuning  is  finished  and  no  error  occurs,  the  warning  automatically 
clears. 
Reset condition  When auto-tuning is finished and no error occurs. 
Record  N/A 
Cause  Corrective Actions 
The motor parameter is running 
auto-tuning 
When the auto-tuning is finished, the warning automatically clears.