Chapter 14 Fault Codes and DescriptionsC2000  Plus 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
87 
O
low frequency (oL3) 
Low frequency and high current protection 
Action and Reset 
Action condition  Software detection 
Action time  Act immediately 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Reset immediately 
Record  Yes 
Cause  Corrective Actions 
Power module overload 
1.  Reduce the motor drive’s load. 
2.  Decrease the carrier frequency (Pr.00-17) 
3.  Decrease the ambient temperature of the drive’s operation 
4.  Decrease the current limit 
5.  Choose motor drives with lager power 
6.  Increases acceleration time 
7.  If the drive is in V/F mode, decrease the output voltage for low-