Chapter 12 Description of Parameter SettingsCP2000
12.1-01-2
Mid-point Frequency 1 of Motor 1
Default: 3.00 / 3.00 /
0.0 / 0.0
Settings 230V series: 0.00–599.00 Hz
460V series: 0.00–599.00 Hz
575V series: 0.00–599.00 Hz
690V series: 0.00–599.00 Hz
Mid-point Voltage 1 of Motor 1
Default: 11.0 / 22.0 /
0.0 / 0.0
Settings 230V series: 0.0–240.0 V
460V series: 0.0–480.0 V
575V series: 0.0–637.0 V
690V series: 0.0–720.0 V
690V, 185 kW and above
series: 10.0
Mid-point Frequency 1 of Motor 2
Default: 3.00
Settings 0.00–599.00 Hz
Mid-point Voltage 1 of Motor 2
Default: 11.0 / 22.0 /
0.0 / 0.0
Settings 230V series: 0.0–240.0 V
460V series: 0.0–480.0 V
575V series: 0.0–637.0 V
690V series: 0.0–720.0 V
690V, 185 kW and above
series: 10.0
Mid-point Frequency 2 of Motor 1
Default: 1.50
Settings 0.00–599.00 Hz
Mid-point Voltage 2 of Motor 1
Default: 5.0 / 10.0 /
0.0 / 0.0
Settings 230V series: 0.0–240.0 V
460V series: 0.0–480.0 V
575V series: 0.0–637.0 V
690V series: 0.0–720.0 V
690V, 185 kW and above
series: 2.0
Mid-point Frequency 2 of Motor 2
Default: 1.50
Settings 0.00–599.00 Hz