Chapter 12 Description of Parameter SettingsCP2000
12.1-06-26
Enable Bypass on Fire Mode
Default: 0
Settings 0: Disable Bypass
1: Enable Bypass
Bypass Delay Time on Fire Mode
Default: 0.0
Settings 0.0–6550.0 sec.
Number of Times of Reset in Fire Mode
Default: 0
Settings 0–10
Length of Time of Reset in Fire Mode
Default: 60.0
Settings 0.0–6000.0 sec.
The settings for Pr.06-82 to Pr.06-85 determine whether to switch motors to operate under
mains electricity when in fire mode.
Fire Mode Motion
Default: 0
Settings bit0: 0=Open Loop; 1=Close Loop (PID control)
bit1: 0=Manual reset fire mode; 1=Auto reset fire mode
0:
Open loop control & manual reset fire mode
1: Close loop control & manual reset fire mode
2: Open loop control & auto reset fire mode
3: Close loop control & auto reset fire mode
Fire Mode PID Set Point
Default: 0.00
Settings 0.00–100.00%
Use Pr.06-87 as the Fire mode PID set point when setting the Pr.06-86 bit0=1.