Chapter 12 Description of Parameter SettingsCP2000
12.1-09-16
BACnet Max Address
Default: 127
Settings 0–127
BACnet Password
Default: 0
Settings 0–65535
Identifications for Communication Card
Default: Read only
Settings 0: No communication card
1: DeviceNet Slave
2: Profibus-DP Slave
3: CANopen Slave / Master
4: Modbus-TCP Slave
5: EtherNet / IP Slave
8: BACnet IP
12: PROFINET
Firmware Version of Communication Card
Default: Read only
Settings Read only
Product Code
Default: Read only
Settings Read only
Error Code
Default: Read only
Settings Read only
Communication Card Address (for DeviceNet or PROFIBUS)
Default: 1
Settings DeviceNet: 0–63
Profibus-DP: 1–125
Communication Card Speed Setting (for DeviceNet)
Default: 2
Settings Standard DeviceNet:
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
3: 1 Mbps (Delta only)
Non standard DeviceNet : (Delta only)
0: 10 Kbps
1: 20 Kbps
2: 50 Kbps
3: 100 Kbps