Chapter 12 Description of Parameter SettingsCP2000
12.1-12-13
Disable Motor’s Output
Set the multi-function input commands to Disable Motors’ Output can stop the corresponding
motors.
The settings are:
Pr.02-01–Pr.02-06= 60 61 62 63 64 65 66 67 68
Disable Motor’s Output ALL 1 2 3 4 5 6 7 8
When a motor’s output is disabled, this motor coasts to stop.
Wiring: Fixed Quantity Control can control up to eight motors. Diagram 12-12 is an example of
controlling four motors at the same time.
R S T
Contactor
M1
L N
M0
Contactor
M2
Contactor
M3
Contactor
M4
U V W
RA2
RC2
RA1
RB 1
RC1
MO3
MO2
MO1
RA3
RC3
MO 6
MO 5
MO 4
R6AA
V
FD-CP2000
Diagram 12-12