EasyManua.ls Logo

Delta VFD1600C43A-21 - Page 420

Delta VFD1600C43A-21
1259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 11 Summary of Parameter SettingsC2000 Plus
11-33
Pr. Parameter Name Setting Range Default
06-15
Temperature Level Overheat (OH)
Warning
0.0–110.0°C
105.0
06-16
Stall Prevention Limit Level
(Weak Magnetic Field Current
Stall Prevention Level)
230V / 460V models: 0–100% (refer to Pr.06-03)
575V / 690V models: 0–100% (refer to Pr.06-03)
100
50
06-17 Fault Record 1
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during steady operation (ocn)
4: Ground fault (GFF)
5: IGBT short-circuit between upper bridge and lower
bridge (occ)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage at constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage at constant speed (Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss protection (OrP)
16: IGBT overheating (oH1)
17: Heatsink overheating (oH2)
18: IGBT temperature detection failure (tH1o)
19: Capacitor hardware error (tH2o)
21: Over load (oL)
22: Electronic thermal relay 1 protection (EoL1)
23: Electronic thermal relay 2 protection (EoL2)
24: Motor overheating (oH3) (PTC / PT100)
25: Interrupt error (INTR)
26: Over torque 1 (ot1)
27: Over torque 2 (ot2)
28: Under current (uC)
29: Limit error (LiT)
30: EEPROM write error (cF1)
31: EEPROM read error (cF2)
33: U-phase error (cd1)
34: V-phase error (cd2)
35: W-phase error (cd3)
0
06-18 Fault Record 2 0
06-19 Fault Record 3 0
06-20 Fault Record 4 0
06-21 Fault Record 5 0
06-22 Fault Record 6 0

Table of Contents

Related product manuals