Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-07-9 
 Situation 4: 
Pr.07-13=2 “dEb active, DC bus voltage returns, the output frequency returns” and power does 
not recover. 
The drive decelerates to 0 Hz. The DC bus voltage continues to decrease until the voltage is 
lower than the Lv level, and then the drive disconnects the soft start relay. The keypad displays 
“dEb” warning until the drive completely runs out of power. 
 Situation 5: 
Pr.07-13=2 “dEb low voltage control, when the speed is lower than 1/4 rated motor speed, DC 
bus voltage rises to 350V
DC 
/ 700V
DC
, the drive ramps to stop. 
The drive decelerates to 0 Hz. The DC bus voltage continues to decrease until the voltage is 
lower than the Lv level, and then the drive disconnects the soft start relay. The soft start relay 
closes again after the power recovers and the DC bus voltage is higher than the Lv return level. 
When the DC bus voltage is higher than the dEb return level, the drive maintains the frequency 
for the set time of Pr.07-14 (default = 3 sec.) and starts to accelerate linearly, and the dEb 
warning on the keypad is automatically cleared. 
 Situation 6:  
Pr.07-13=4, dEb high-voltage control 
When dEb occurs, the DC bus voltage control level rises to 350V
DC 
/ 700V
DC
 to ramp to stop. 
Even though the power recovers and the frequency does not return, dEb activates until the 
motor decelerates to 0Hz.   
(1) When dEb activates, it sends dEb warning. When the output frequency reaches 0Hz, the 
operation status is STOP and disables the dEb function, the dEb warning continues. 
(2) If power does not recover, the DC bus voltage drops until reaches the Lv level, the drive 
LvS error occurs (keypad displays LvS error that covers the dEb display), the Soft Start 
Relay will be OFF. 
 
07-14 
dEb Function Reset Time 
 
 
   
 Default: 3.0 
 
 
Settings 0.0–25.0 sec. 
 dEb (Deceleration Energy Backup) lets the motor decelerate to stop when momentary power loss 
occurs. When the power loss is instantaneous, use this function to let the motor decelerate to zero 
speed. 
 
07-15 
Dwell Time at Acceleration 
 
 
   
 Default: 0.00 
 
 
Settings 0.00–600.00 sec. 
 
07-16 
Dwell Frequency at Acceleration 
 
 
   
 Default: 0.00 
 
 
Settings 0.00–599.00 Hz 
 
07-17 
Dwell Time at Deceleration 
 
 
   
 Default: 0.00 
 
 
Settings 0.00–600.00 sec.